O-54 Reversing Select
Option:
Function:
[0]
Digital
input
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
[1]
Bus
Activates the Reverse command via the serial
communication port or fieldbus optionmodule.
[2]
Logic AND
Activates the Reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the Reverse command via the
fieldbus/serial communication port OR via one
of the digital inputs.
O-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-
up selection via the terminals (digital input)
and/or via the network.
[0]
Digital
input
Activates the set-up selection via a digital
input.
[1]
Bus
Activates the set-up selection via the serial
communication port or network option
module.
[2]
Logic AND
Activates the set-up selection via the network/
serial communication port, AND additionally via
one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the network/
serial communication port OR via one of the
digital inputs.
O-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter
Preset Reference selection via the terminals
(digital input) and/or via the network.
[0]
Digital
input
Activates Preset Reference selection via a
digital input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port or network option
module.
[2]
Logic AND
Activates Preset Reference selection via the
network/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the Preset Reference selection via the
network/serial communication port OR via one
of the digital inputs.
3.10.6 O-8# Drive Port Diagnostics
O-80 Bus Message Count
Range:
Function:
0
*
[0 - 0] This parameter shows the number of valid
messages detected on the network.
O-81 Bus Error Count
Range:
Function:
0
*
[0 - 0] This parameter shows the number of messages with
faults (e.g. CRC fault), detected on the network.
O-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 0] This parameter shows the number of valid
messages addressed to the slave, sent by the
frequency converter.
O-83 Slave Error Count
Range:
Function:
0
*
[0 - 0] This parameter shows the number of error
messages, which could not be executed by the
frequency converter.
3.10.7 O-9# Bus Jog Feedback
Parameters to configure the Jog Speed when drive is in
Bus Control.
O-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[0 - par. F-17
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or network option.
O-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
*
[0 - par. F-17
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or network option.
Parameter Descriptions
AF-650 GP Programming Guide
92
DET-618C
3