1.6.3 Pulse Start/Stop
Terminal 18 =
E-01 Terminal 18 Digital Input
Latched start,
[9]
Terminal 27=
E-03 Terminal 27 Digital Input
Stop inverse, [6]
Terminal 37 = Safe stop (where available)
Illustration 1.7 Pulse Start/Stop
1.6.4 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 =
E-01 Terminal 18 Digital Input
Start
[9] (default)
Terminal 27 =
E-03 Terminal 27 Digital Input
Freeze reference [19]
Terminal 29 =
E-04 Terminal 29 Digital Input
Speed up [21]
Terminal 32 =
E-05 Terminal 32 Digital Input
Speed down [22]
Illustration 1.8 Speed Up/Down
1.6.5 Potentiometer Reference
Voltage reference via a potentiometer
Reference Source 1 =
[1] Analog input 53
(default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Illustration 1.9 Potentiometer Reference