AN-50 Terminal 42 Output
Option:
Function:
must be:
Imotor x 100%/Imax = 22 A x 100%/38.4 A =
57%
[104] Torque rel
to limit
The torque setting is related to setting in
[105] Torq relate
to rated
The torque is related to the motor torque
setting.
[106] Power
[107] Speed
. 20 mA =
value in
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
Freq
0 Hz = 0 mA,
=
20 mA.
[113] PID
Clamped
Output
[119] Torque %
lim
Torque% lim: Torque reference.
[Min - Max] 0% = 0 mA; 100% = 20 mA
[-Max - Max] -100% = 0
mA; 0% = 10 mA; +100% = 20 mA
[130] Output
freq.
4-20mA
0 Hz = 4 mA, 100 Hz = 20 mA
[131] Reference
4-20mA
[Min-Max] 0% = 4 mA;
100% = 20 mA
[-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback
4-20mA
Feedback 4-20 mA:
[Min-
Max] 0% = 4 mA; 100% = 20 mA
[-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[133] Motor cur.
4-20mA
Inverter max. current (160% current) is equal
to 20 mA.
[134] Torq.% lim
4-20 mA
The torque setting is related to setting in
[135] Torq.%
nom
4-20mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
[137] Speed
4-20mA
. 20 mA =
Value in
.
[138] Torque
4-20mA
Torque reference related to 160% torque.
[139] Bus ctrl.
0-20 mA
An output value set from Network process
data. The output will work independently of
internal functions in the frequency converter.
AN-50 Terminal 42 Output
Option:
Function:
[140] Bus ctrl.
4-20 mA
An output value set from Network process
data. The output will work independently of
internal functions in the frequency converter.
[141] Bus ctrl
0-20mA t.o.
defines the
behaviour of the analog output in case of bus
time-out.
[142] Bus ctrl
4-20mA t.o.
defines the
behaviour of the analog output in case of bus
time-out.
[149] Torque %
lim 4-20mA
Analog output at zero torque = 12 mA.
Motoric torque will increase the output
current to max torque limit 20 mA (set in
Generative torque will decrease the output to
torque limit Generator Mode (set in
Ex:
: 200% and
: 200%. 20 mA =
200% Motoric and 4 mA = 200% Generatoric.
Illustration 3.33
[150] Max Out Fr
4-20mA
0 Hz = 0 mA,
=
20 mA.
AN-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 - 200
%]
Scale for the minimum output (0 or 4 mA) of
the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
AN-50 Terminal 42 Output
.
AN-52 Terminal 42 Output Max Scale
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal 42. Set the value to
the maximum value of the current signal output.
Scale the output to give a current lower than 20
mA at full scale; or 20 mA at an output below
100% of the maximum signal value. If 20 mA is
the desired output current at a value between 0
- 100% of the full-scale output, program the
percentage value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20 mA is desired
at maximum output (100%), calculate the
percentage value as follows:
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
75
3