F-52 Minimum Reference
Range:
Function:
closed loop
, RPM;
for
[2] Torque
, Nm.
•
The unit selected
in
.
F-53 Maximum Reference
Range:
Function:
1500.000
ReferenceFeed-
backUnit
*
[par. F-52 -
999999.999
ReferenceFeed-
backUnit]
Enter the Maximum
Reference. The Maximum
Reference is the highest
value obtainable by
summing all references.
The Maximum Reference
unit matches:
•
The choice of
: for
[1] Speed
closed loop
, RPM;
for
[2] Torque
, Nm.
•
The unit selected
in
F-54 Reference Function
Option:
Function:
[0]
*
Sum
Sums both external and preset reference
sources.
[1]
External/Preset Use either the preset or the external
reference source.
Shift between external and preset via a
command or a digital input.
3.3.8 F-6# References
Parameters to configure drive to add or subtract a fixed
value to an input reference.
F-62 Catch up/slow Down Value
Range:
Function:
0 %
*
[0 -
100 %]
Enter a percentage (relative) value to be either
added to or deducted from the actual reference
for Catch up or Slow down respectively. If
Catch
up
is selected via one of the digital inputs
(
E-01 Terminal 18 Digital Input
to
E-06 Terminal 33
Digital Input
), the percentage (relative) value is
added to the total reference. If
Slow down
is
selected via one of the digital inputs
(
E-01 Terminal 18 Digital Input
to
E-06 Terminal 33
Digital Input
), the percentage (relative) value is
deducted from the total reference. Obtain
F-62 Catch up/slow Down Value
Range:
Function:
extended functionality with the DigiPot function.
See parameter group
F-9# Digital Pot-Meter
.
F-64 Preset Relative Reference
Range:
Function:
0 %
*
[-100 -
100 %]
The actual reference, X, is increased or
decreased with the percentage Y, set in
F-64 Preset Relative Reference
. This results in the
actual reference Z. Actual reference (X) is the
sum of the inputs selected in
F-01 Frequency
Setting 1
,
C-30 Frequency Command 2
,
C-34 Frequency Command 3
and
O-02 Control
Word Source
.
Illustration 3.12 Preset Relative Reference
Illustration 3.13 Actual Reference
F-68 Relative Scaling Reference Resource
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Select a variable value to be added to the
fixed value (defined in
). The sum of the fixed and
variable values (labelled Y in
) is multiplied with the actual
reference (labelled X in
).
This product is then added to the actual
reference (X+X*Y/100) to give the resultant
actual reference.
Parameter Descriptions
AF-650 GP Programming Guide
40
DET-618C
3
3