[72]
Logic Rule 2
See parameter group LC-4#. If Logic Rule
2 is evaluated as TRUE, the output will
go high. Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group LC-4#. If Logic Rule
3 is evaluated as TRUE, the output will
go high. Otherwise, it will be low.
[74]
Logic Rule 4
See parameter group LC-4#. If Logic Rule
4 is evaluated as TRUE, the output will
go high. Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group LC-4#. If Logic Rule
5 is evaluated as TRUE, the output will
go high. Otherwise, it will be low.
[80]
Logic Controller
Digital Output
A
See
. The
output will go high whenever the Logic
Controller Action
[38] Set dig. out. A high
is executed. The output will go low
whenever the Logic Controller Action
[32] Set dig. out. A low
is executed.
[81]
Logic Controller
Digital Output B
See
. The
input will go high whenever the Logic
Controller Action
[39] Set dig. out. A high
is executed. The input will go low
whenever the Logic Controller Action
[33] Set dig. out. A low
is executed.
[82]
Logic Controller
Digital Output
C
See
. The
input will go high whenever the Logic
Controller Action
[40] Set dig. out. A high
is executed. The input will go low
whenever the Logic Controller Action
[34] Set dig. out. A low
is executed.
[83]
Logic Controller
Digital Output
D
See
. The
input will go high whenever the Logic
Controller Action
[41] Set dig. out. A
high
is executed. The input will go low
whenever the Logic Controller Action
[35] Set dig. out. A low
is executed.
[84]
Logic Controller
Digital Output E
See
. The
input will go high whenever the Logic
Controller Action
[42] Set dig. out. A high
is executed. The input will go low
whenever the Logic Controller Action
[36] Set dig. out. A low
is executed.
[85]
Logic Controller
Digital Output F
See
. The
input will go high whenever the Logic
Controller Action
[43] Set dig. out. A high
is executed. The input will go low
whenever the Logic Controller Action
[37] Set dig. out. A low
is executed.
[120] Local reference
active
Output is high when
= [2] Local or when
=
[0] Linked to
hand auto
at the same time as the
keypad is in Hand mode.
[121] Remote
reference active
Output is high when
=
[1] Remote
or
[0] Linked to
hand/auto
while the keypad is in [Auto]
mode.
[122] No alarm
Output is high when no alarm is present.
[123] Start command
active
Output is high when there is an active
Start command (i.e. via digital input bus
connection or [Hand] or [Auto]), and no
Stop or Start command is active.
[124] Running reverse Output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ AND ‘reverse’).
[125] Drive in hand
mode
Output is high when the frequency
converter is in [Hand mode] (as indicated
by the LED light above [Hand]).
[126] Drive in auto
mode
Output is high when the frequency
converter is in [Hand] mode (as indicated
by the LED light above [Auto]).
E-20 Terminal 27 Digital Output
Choices are described under E-2#
E-21 Terminal 29 Digital Output
Choices are described under E-2#
E-24 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay
6 [5], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Choices are described under E-2#
E-26 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-in time.
The relay will only cut in if the condition
in
E-24 Function Relay
is uninterrupted
during the specified time. Select one of
available mechanical relays and OPCRLY
Relay Option Module in an array
function. See
E-24 Function Relay
.
Illustration 3.16 On Delay, Relay
Parameter Descriptions
AF-650 GP Programming Guide
48
DET-618C
3
3