3.9.1 SP-1# Line On/Off
Parameters to configure actions taken for Line Failures,
Input Fault, and Imbalance.
SP-10 Line failure
Option:
Function:
is typically used where very short
mains interruptions (voltage dips) are present. At
100% load and a short voltage interruption, the
DC voltage on the main capacitors drops quickly.
For larger drives it only takes a few milliseconds
before the DC level is down to about 373 V DC
and the IGBTs cut off and looses the control over
the motor. When the mains is restored, and the
IGBTs start again, the output frequency and
voltage vector does not correspond to the speed/
frequency of the motor, and the result is normally
an overvoltage or overcurrent, mostly resulting in
a trip lock.
can be programmed
to avoid this situation.
Select the function to which the frequency
converter must act when the threshold in
SP-11 Line Voltage at Input Fault
has been reached.
cannot be changed while motor
is running.
[0]
*
No
function
The frequency converter will not compensate for a
mains interruption. The voltage on the DC-link will
drop quickly and motor control will be lost within
milliseconds to seconds. Trip lock will be the
result.
[1] Ctrl.
Decel
The frequency converter will remain control of the
motor and do a controlled ramp down from
SP-11 Line Voltage at Input Fault
is
[0] Off
or
[2] AC brake
, the ramp will
follow the Over Voltage Ramping. If
is
[1] Resistor Brake
the ramp will follow
the setting in
. This
selection is particularly useful in pump
applications, where the inertia is low and the
friction is high. When the mains is restored, the
output frequency will ramp the motor up to the
reference speed (if the mains interruption is
prolonged, the controlled ramp down might take
the output frequency all the way down to 0 RPM,
and when the mains is restored, the application is
ramped up from 0rpm to the previous reference
speed via the normal ramp up). If the energy in
the DC-link disappears before the motor is
ramped to zero the motor will be coasted.
[2] Ctrl.
Decel,
trip
This selection is similar to selection [1] except that
in [2] a reset is necessary for starting up after
power-up.
[3] Coasting
Centrifuges can run for an hour without power
supply. In those situations it is possible to select a
SP-10 Line failure
Option:
Function:
coast function at mains interruption, together with
a flying start which occurs when the mains is
restored.
[4] Kinetic
back-up
Kinetic back-up ensures that the frequency
converter keeps running as long as there is
energy in the system due to the inertia from
motor and load. This is done by converting the
mechanical energy to the DC-link and thereby
maintaining control of the drive and motor. This
can extend the controlled operation, depending
on the inertia in the system. For fans it is typically
several seconds, for pumps up to 2 seconds and
for compressors only for a fraction of a second.
Many industry applications can extend controlled
operation for many seconds, which is often
enough time for the mains to return.
Illustration 3.35 Kinetick Back-up
A Normal operation
B Mains failure
C Kinetic back-up
D Mains return
E
Normal Operation: ramping
Table 3.17 Legend to
The DC-level during
[4] Kinetic back-up
is
SP-11 Line Voltage at Input Fault
* 1.35.
If the mains do not return U
DC
is maintained as
long as possible by ramping the speed down
towards 0 RPM. Finally the frequency converter
coasts.
If the mains return while in kinetic back-up U
DC
*1.35. This is detected in one of the following
ways.
1.
If U
DC
>
*1.35*1.05
2.
If the speed is above the reference. This
is relevant if the mains come back at a
lower level than before, e.g.
*1.35*1.02. This
does not fulfil the criterion in point one
and the frequency converter will try to
Parameter Descriptions
AF-650 GP Programming Guide
78
DET-618C
3
3