F-43 Current Limit
Range:
Function:
160.0
%
*
[1.0 -
1000.0 %]
This is a true current limit function that
continues in the oversynchronous range,
however due to field weakening the
motor torque at current limit will drop
accordingly when the voltage increase
stops above the synchronised speed of
the motor.
3.3.7 F-5# Extended References
Parameters to configure drive min/max reference and
reference function.
F-50 Reference Range
Option:
Function:
Select the range of the reference signal and the
feedback signal. Signal values can be positive
only, or positive and negative. The minimum
limit may have a negative value, unless
[1] Speed
closed loop
control or
[3] Process
is selected in
.
[0]
Min -
Max
Select the range of the reference signal and the
feedback signal. Signal values can be positive
only, or positive and negative. The minimum
limit may have a negative value, unless
[1] Speed
closed loop
control or
[3] Process
is selected in
.
[1]
*
-Max -
+Max
For both positive and negative values (both
directions, relative to
F-51 Reference/Feedback Unit
Option:
Function:
Select the unit to be used in Process PID Control
references and feedbacks.
must be either
[3] Process
or
[8] Extended
PID Control
.
[0]
*
None
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
F-51 Reference/Feedback Unit
Option:
Function:
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft3/s
[126] ft3/min
[127] ft3/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[150] lb ft
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
F-52 Minimum Reference
Range:
Function:
0 Reference-
FeedbackUnit
*
[-999999.999 -
par. F-53
ReferenceFeed-
backUnit]
Enter the Minimum
Reference. The Minimum
Reference is the lowest
value obtainable by
summing all references.
Minimum Reference is active
is set to
[0] Min.- Max.
The Minimum Reference
unit matches:
•
The choice of
configuration in
Configuration
Mode
: for
[1] Speed
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
39
3