E-27 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-out time.
Select one of available mechanical relays
and OPCRLY Relay Option Module in an
array function. See
E-24 Function Relay
.
Illustration 3.17 Off Delay, Relay
If the selected Event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
E-51 Terminal 27 Mode
Option:
Function:
NOTE
This parameter cannot be adjusted while the
motor is running.
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output Defines terminal 27 as a digital output.
E-52 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
E-53 Terminal X30/2 Digital Input
Option: Function:
The options are the same as listed for parameter group
E-0#.
E-54 Terminal X30/3 Digital Input
Option: Function:
The options are the same as listed for parameter group
E-0#.
E-55 Terminal X30/4 Digital Input
Option: Function:
The options are the same as listed for parameter group
E-0#.
E-56 Term X30/6 Digi Out (OPCGPIO)
This parameter is active when OPCGPIO General Purpose I/O
Option Module is mounted in the frequency converter. Functions
are described under
E-2# Digital Outputs
.
E-57 Term X30/7 Digi Out (OPCGPIO)
This parameter is active when OPCGPIO General Purpose I/O
Option Module is mounted in the frequency converter. Functions
are described under
E-2# Digital Outputs
.
3.4.4 E-6# Pulse Input
Parameters to configure terminal 29 and 33 as Pulse Train
inputs.
E-60 Term. 29 Low Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the low frequency limit
corresponding to the low motor shaft
speed (i.e. low reference value) in
E-62 Term. 29 Low Ref./Feedb. Value
Refer to the diagram in this section.
E-61 Term. 29 High Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (i.e. high reference value) in
E-63 Term. 29 High Ref./Feedb. Value
E-62 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the low reference
value limit for the motor
shaft speed [RPM]. This
is also the lowest
. Set
terminal 29 to digital
input (
=
[0] input
(default) and
E-04 Terminal 29 Digital
Input
= applicable
value).
E-63 Term. 29 High Ref./Feedb. Value
Range:
Function:
1500.000 Referen-
ceFeedbackUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the high reference
value [RPM] for the
motor shaft speed and
the high feedback value,
see also
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
49
3
3