© Fulton Group N.A., Inc. 2021
WARRANTY & PARTS
ModSyncSE-User-Manual-211020
SECTION 6
6-2
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
67
Factory Default Settings
Lead/Lag Configuration
System Configuration
Shoulder Design
Lead/Lag configuration
Cycles to Auto Rotate
20
Lead Rotation Priority
Manual
Hours to Auto Rotate
10
Manual Rotation Priority
Hours
Max # of Boilers to Run
User Defined at Startup
Setpoint Scaling
Low
High
Lag Boiler Start Delay
1:00
1:00
80
180
Lag Boiler Stop Delay
1:00
1:00
System Configuration
Lag Boiler Start
5
5
Boilers
User Defined
Lag Boiler Stop
5
5
Transition Delay
Enabled
Modulation at Next Stage CV
20
20
Screen Contrast
100
1
st
Lag Stage Start CV
20
20
Temp Scaling
Deg F
1
st
Lag Stage Stop CV
10
10
Modulation Mode
Parallel
Additional Lag Enabled CV
10
10
Outlet Monitoring
Proportional Band
60
60
Enable/Disable
Enable
Integral Time
20
20
Temp > SP By
25
Derivative Time
0
0
Low Fire %
0
Setpoint Configuration
Temp Deviation
10
Setpoint Mode
Modsync
Outlet Scaling
Low
High
Manual Setpoint
120
0
210
DHW Priority
Disabled
-If- Oil Configuration is Required
DHW Min Setpoint
120
Operation in Oil
Modulation
Minimum Setpoint
80
Min SP on Oil
160
Maximum Setpoint
180
Oil High Fire S2
80
-If- Outdoor Sensor is Enabled
Oil Low Fire S1
20
Outdoor Temp Disable
100
Boiler Alarm Config
Outdoor Temp Deviation
5
Boiler Alarm Delay
00:02
Occupied Mode Reset Curve
Loop
OA
Sensor Alarm Delay
00:30
120.0
50.0
Enable after Alarm
Auto
160.0
0.0
Boiler Monitor Alarm
Enabled
Unoccupied Reset Curve
Boiler Monitor Delay
05:00
110.0
50.0
Boiler Monitor Retry
Enabled
150.0
0.0
Monitor Retry Delay
10:00
Setback Schedule Configuration
-If- System Pumps are Enabled
Occupied Unoccupied
Pump Monitor Alarm
Enabled
Monday
6:00
20:00
Pump Monitor Delay
05:00
Tuesday
6:00
20:00
Pump Monitor Retry
Enabled
Wednesday
6:00
20:00
Monitor Retry Delay
10:00
Thursday
6:00
20:00
-If- Proving Interlock is Enabled
Friday
6:00
20:00
Proving Interlock Alarm
Enabled
Saturday
8:00
18:00
Interlock Alarm Delay
00:30
Sunday
8:00
18:00
Factory Default Settings