MAINTENANCE
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
Backing up the Program
Used so that the program is not lost when replacing the battery or the controller
is powered down. Works for Color, SC, and LX screens only. Note: This process
does not save customer settings.
1. Press and hold the screen for 5-10 seconds
until the ‘Info Mode’ Screen
is displayed. Select ‘
Enter Info Mode
’.
2. Enter the password of ‘
1 1 1 1
‘and then press enter.
3. Select ‘
Flash Memory
’ from the ‘Information Mode Main Menu’.
4. Select ‘
Backup User Application
’ from the ‘Flash Memory’ menu.
5. Select ‘
Yes’
. The Controller will now cycle and backup the program. This
could take several minutes.
6. When complete the DLU with display ‘
This app is already backed up’
.
Press ‘
ESC’
three times to exit Info Mode.
Battery Replacement
A 3V coin style lithium battery with part number CR2450N is installed in every
ModSync® screen. The battery is responsible for the backup of the program,
system data, and user settings. It is recommended that the battery be replaced
annually to prevent issues such as loss of program or customer settings.
Common Trouble Shooting Issues
Issue
Explanation / Recommended Action
The Boiler Outlet temperature
displayed at the ModSync® does
not match what is shown on the
local boiler controls for 4-20mA
applications.
This is commonly seen on boilers with the
Siemens LMV3 controls. Check that the Outlet
temperature scaling in the ModSync® matches
the scaling in the local boiler controls. The
most common are 0-210F and 0-240F.
The Protonode is not
communicating with the
ModSync® (Rx and Tx are not
flashing)
Check that the Protonode is connected to Port
2 on the ModSync® using the factory supplied
cable. The Port 2 settings on the BMS Config
page should be set up for a node address of 2
and baud rate of 19200.
The Boiler is tripping on its high
limit while under ModSync®
control.
Check that the Maximum setpoint plus any
deviation is set at least 10F below the high
limit of the boilers. Check flow through the
boilers including isolation valve and pump
operation.
ModSync® displays *** for
temperatures instead of a value.
The ModSync® sensor reading is out of range.
Check wiring and sensor operation.