Analog Outputs:
All analog outputs need to be configured for the options
desired before the outputs will operate. Only options that have been
enabled will be selectable. All analog outputs are 4-20mA.
»
Boiler # Pump VFD:
Configures the output to control the boiler
circulator pump’s VFD. This selection will only be available if Boiler
Pumps are enabled and the VFD selection has been enabled.
»
System Pump # VFD:
Configures the output to control the System
Pump’s VFD. This selection will only be available if System Pump are
enabled and the VFD selection has been enabled.
FIGURE 14 – ANALOG OUTPUT HARDWARE CONFIGURATION SCREEN