© Fulton Group N.A., Inc. 2021
6-6
WARRANTY & PARTS
ModSyncSE-User-Manual-211020
SECTION 6
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
Specifications
Mechanical:
Size:
Height: 16.55”; Width: 14.55”;
Depth:
8.31”
(Typical)
Weight:
22 lbs.
Environmental:
Operating Temp:
32ºF to 110ºF (0ºC to 43ºC)
Storage Temp:
-20ºF to 130ºF (-28ºC to 54ºC)
Front Panel:
NEMA 1, IP65
Electrical:
Input Power:
120 VAC (+/- 10%), less than 2 Amps.
Agency Listings:
UL 508A – Industrial Control Panels
Wiring:
Modbus:
RS485 Shielded (6-pin RJ-11 connector) for
ModSync® Port 2 (BMS Network) or Port 3
(Boiler Network). 18-24 gauge shielded wire
with three (3) conductors plus the shield.
Note that the Shield is not the third conductor
and is terminated separately at a designated
SHLD or GND terminal at only one end,
location, or panel in the network.
Daisy chain configuration only using line
network topology. Modbus RS485 Maximum
network length is 4,000 ft with a maximum of
32
devices.
Analog:
For 4-20mA and 0-10VDC use 18-24 gauge
shielded wire. The shield gets terminated
separately at a designated SHLD or GND
terminal at only one end, location, or panel
in
the
network
For RTD sensors use 20-24 gauge three (3)
conductor wire. Maximum length for RTD
wiring
is
200ft.
Digital I/O:
18-gauge wire (Blue 24VDC(+),
Yellow
24VDC(-)
)