Lead / Lag Configuration 2
Lag Boiler Start Delay:
Defined in units of Minutes/Seconds. Determines
the time required before the ModSync® will enable a lag boiler after it has
reached its enable point.
Lag Boiler Stop Delay:
Defined in units of Minutes/Seconds. Determines
the time required before the ModSync® will disable a lag boiler after it has
reached its disable point.
Lead Boiler Start Deviation:
Defines how many degrees below setpoint
before the ModSync® will enable the lead boiler.
Lead Boiler Stop Deviation
: Defines how many degrees above setpoint
before the ModSync® will disable the lead boiler.
FIGURE 29 – LEAD / LAG SCREENS PAGE 2