208
Upgrade and Maintenance Manual
CX250
S2
Processors
Figure 120: Heat sink types
Ê
Remove the protective cover from the heat sink.
I
Ensure not to touch the thermal paste on the bottom of the heat sink.
Ê
Install the processor heat sink as described in section
"Installing the
processor heat sink" on page 201
.
8.3.5
Concluding steps
Perform the following steps:
Ê
"Installing the server node in the server enclosure" on page 63
Ê
"Updating or recovering the system board BIOS and BMC" on page 67
(if
applicable)
Ê
"Switching on the server node" on page 64
Ê
"Enabling boot watchdog functionality" on page 74
1 Heat sink for CPU0
2 Heat sink for CPU1