BX900 S2
Upgrade and Maintenance Manual
147
Management Blades
Ê
Take a note of the firmware version of the master management blade as
described in section
"Looking up the management blade firmware version"
on page 66
.
9.3.3
Removing the defective management blade
Ê
Remove the defective management blade.
A management blade is removed in the same way as a single-width
connection blade as described in section
"Removing a single-width
connection blade" on page 116
.
9.3.4
Installing the management blade
Ê
Unpack the management blade.
Ê
Install the management blade in the system unit.
A management blade is installed in the same way as a single-width
connection blade as described in section
"Installing a single-width
connection blade" on page 113
.
9.3.5
Concluding steps
Perform the following procedures to complete the task:
Ê
Wait until the boot process of new management blade has finished.
Ê
If one management blade is installed, connect a field service terminal to the
management blade as described in section
"Accessing the management
blade web interface" on page 44
.
Ê
Check the firmware version of the new management blade as described in
section
"Looking up the management blade firmware version" on page 66
.
Ê
If applicable, update the firmware of the new management blade as
described in section
"Updating / recovering the management blade
firmware" on page 66
.
Ê
If two management blades are installed, check the management blade
master/slave behavior as described in section
"Checking management
master/slave behavior" on page 73
.