BX900 S2
Upgrade and Maintenance Manual
145
Management Blades
A management blade dummy module is removed in the same way as a
connection blade dummy module as described in section
"Removing
connection blade dummy module" on page 113
.
V
CAUTION!
Keep the dummy module for future use.
Always replace the management blade dummy module into an unused
management blade slot to comply with applicable EMC regulations and
satisfy cooling requirements.
9.2.4
Installing the management blade
Ê
Unpack the management blade.
Ê
Install the management blade in the system unit.
A management blade is installed in the same way as a single-width
connection blade as described in section
"Installing a single-width
connection blade" on page 113
.
9.2.5
Concluding steps
Perform the following procedures to complete the task:
Ê
Wait until the boot process of new management blade has finished.
Ê
Check the firmware version of the new management blade as described in
section
"Looking up the management blade firmware version" on page 66
.
Ê
If applicable, update the firmware of the new management blade as
described in section
"Updating / recovering the management blade
firmware" on page 66
.
Ê
Check the management blade master/slave behavior as described in
section
"Checking management master/slave behavior" on page 73
.
Ê
Verify the time settings of the new management blade as described in
section
"Verifying the management blade time settings" on page 70
.
Ê
Disconnect the field service terminal from the management blade.
Ê
If applicable, close the rack door as described in section
"Closing the rack
door" on page 60
.