CONTROL AND MONITORING ITEMS
NOTE: For detail information, check the Interface
Specificatio
n.
Item
Function
Description
Indoor Unit
Control
(Individual /
Batch)
ON/OFF Command
Start / Stop operation
Operation Mode Setting
Cooling / Heating / Auto / Fan / Dry
Temperature Setting
Set room temperature
Airflow Mode Setting
Set airflow
Set Point Temperature Limit Setting
Set room temperature lower limit (for cooling
mode) & room temperature upper limit (for
heating mode)
Thermostat Off setting
Thermostat off
(Only one controller in VRF Network System can
do this)
Centrally Control (Filter Reset)
Prohibition of filter sign reset of remote controller
Centrally Control (All Mode )
Prohibition of all mode of remote controller
Centrally Control (Timer Mode)
Prohibition of timer mode of remote controller
Centrally Control (Set Temperature Mode) Prohibition of set temperature mode of remote
controller
Centrally Control (ON/OFF Mode)
Prohibition of ON/OFF mode of remote controller
Centrally Control (ON Mode)
Prohibition of ON mode of remote controller
Centrally Control (Operation Mode)
Prohibition of operation mode of remote controller
Indoor Unit
Control
(Individual)
Filter Sign Reset
Set filter sign reset command
Antifreeze Setting
Set antifreeze command
Energy Save Mode Setting
Set energy save command
Indoor Unit
Control
(Batch)
Emergency STOP Setting
Set Emergency STOP command
Time Setting
Set time setting command
(The controllers those are connected in VRF
Network System are an object)
Indoor Unit
Monitoring
(Individual)
ON/OFF Status
ON / OFF status
Operation Mode Setting Status
Heating / Cooling / Auto / Fan / Dry mode status
Temperature Setting Status
Room set temperature status
Airflow Mode Setting Status
Airflow mode status
Set Point Temperature Limit Status
Room set temperature limit status
Thermostat Off Setting Status
Thermostat off set value status
Centrally Control (Filter Reset) Status
Remote controller filter reset prohibition status
Centrally Control (All Mode ) Status
Remote controller all mode prohibition status
Centrally Control (Timer Mode) Status
Remote controller timer mode prohibition status
Centrally Control (Set Temperature) Status Remote controller set temp. prohibition status
Centrally Control (ON/OFF ) Status
Remote controller ON / OFF prohibition status
Centrally Control (ON ) Status
Remote controller ON prohibition status
Centrally Control (Operation ) Status
Remote controller operation prohibition status
Antifreeze Setting Status
Antifreeze set status
Energy Save Mode Setting Status
Energy save mode set status
Filter Sign Reset Status
Filter sign reset status
Room Temperature Status
Room temperature status
Error Code Status
Only one Error Code status can be monitored
Operation Mode restriction Status
Restriction item (*1) can be monitored
Indoor Unit
Monitoring
(Batch)
Maintenance Mode Status
Maintenance status
Emergency STOP Setting Status
Emergency STOP setting status
Outdoor Unit
Monitoring
(Individual)
Error Code Status
Error code status
Convertor Unit
Monitoring
(Individual)
Error Code Status
Error code status
*1: All operation setting, Timer setting, Room temperature setting, Operation mode setting, ON/OFF operation, Filter reset
operation, On operation setting.
- (05 - 138) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...