SETTING OF OUTDOOR UNIT AND SYSTEM CONTROLLER OR
TOUCH PANEL CONTROLLER
To obtain the appropriate Input Power by System Controller or Touch Panel Controller,
the power value measured by an electricity meter must be properly conveyed. To do this,
appropriate setting at the electricity meter, outdoor unit, and System Controller or Touch Panel
Controller is necessary. The method of setting the pulse from the electricity meter received by
an outdoor unit and the method of setting the pulse value set by System Controller or Touch
Panel Controller are described here. When electricity meter setting is necessary, perform it in
accordance with the instruction manual supplied with the electricity meter.
Below, the setting method of electricity meters specified in pulse units and that specified in
pulse constant are described.
(1) When electricity meter used is specified in pulse units
The connection configuration is shown below
.
Pulse unit
reference
point
measurement
ine
measurement
line
pulse
transmission
line
pulse transmission line
CT
VT
(PT)
3ø
1ø
VT
(PT)
System Controller
Transmission line
(VRF Network)
Outdoor unit
Indoor unit
RB unit
Power cable
Electricity meter
Electricity meter
to CN135
to CN135
Touch panel
controller
For the electricity meter specified in pulse units, the output pulses are normalized in advance
(normally 1kWh/pulse) and is output. In this case, the settings are as follows:
Set point
Set item
Set value
Description
Remarks
Electricity
meter
Set in
accordance
with the product
manual.
-
When there is a product unique setting,
setting is performed in accordance with
the product manual. (Pulse units value,
VT/CT ratio, output coefficient, etc.)
Outdoor unit Meter No.
setting
Arbitrary
Set an unique electricity meter No. for
electricity meter identification.
The information
will become
necessary when
setting System
Controller or ECA
Tool later.
Refer also to
2-1 OUTDOOR
UNIT.
Electricity meter
pulse setting
1
Fixed to “1”.
When 1 pulse comes from the
electricity meter, the outdoor unit
communicates “1” to the System
Controller or ECA Tool.
System
Controller or
ECA Tool
Electricity meter
system setting
Units measured by
electricity meter
Set the outdoor unit and indoor unit,
measured by the electricity meter of the
meter No. set at the outdoor unit.
The value set by
each outdoor unit
is used.
Pulse setting
Electricity meter pulse
units value (Usually
either of 1, 10, or 100
[kWh/ pulse])
Set the pulse units specified by the
electricity meter as they are.
Set the number of kWh that
corresponds to the “1” communicated
from the outdoor unit.
Refer to the
value set by each
outdoor unit.
[
Setting example]
Equipment conditions: VT ratio=1 (not used), CT ratio=50(250/5A), electricity meter=1kWh/pulse
Set value: Electricity meter pulse setting=1(fixed), pulse setting=1(corresponds to electricity meter used)
- (07 - 170) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...