BACnet
®
OBJECT LIST
z
Type : Indoor
Object
name
Code
(II)
Function
Unit
Inactive
Active
Text-1
Text-2
Text-3
Text-4
Text-5
Text-6
Text-7
AI
10
Set temp. status
Degree
11
Space temp.
Degree
12
Auto temp. (Low limit status)
Degree
13
Auto temp. (High limit status)
Degree
14
Cool/Dry temp. (Low limit status)
Degree
15
Cool/Dry temp. (High limit status)
Degree
16
Heat temp. (Low limit status)
Degree
17
Heat temp. (High limit status)
Degree
AO
10
Temp. setting
Degree
11
Auto temp. (Low limit setting)
Degree
12
Auto temp. (High limit setting s)
Degree
13
Cool/Dry temp. (Low limit setting )
Degree
14
Cool/Dry temp. (High limit setting ) Degree
15
Heat temp. (Low limit setting )
Degree
16
Heat temp. (High limit setting )
Degree
AV
10
ECA *1 operation data
BI
10
Operation status
OFF
ON
14
Filter sign status
Unsigned
Signed
15
Indoor unit error status
Normal
Fault
16
Antifreeze operation status
Reset
Set
17
SAVE operation status
Normal
SAVE
18
Forced thermostat off status
Reset
Set
19
Emergency stop status
Normal
Stop
20
Mode mismatch status
Normal
Mismatch
21
Protect antifreeze status
Reset
Set
22
Temp. limit valid status
Invalid
Valid
BO
10
Operation setting
OFF
ON
14
Filter sign resetting
Reset
Not reset
15
Antifreeze operation setting
Reset
Set
16
SAVE operation setting
Reset
Set
17
Forced thermostat OFF setting
Reset
Set
18
Emergency stop setting
Reset
Set
19
Temp. limit valid setting
Invalid
Valid
MI
10
Operation mode status
Cool
Heat
Fan
Dry
Auto
11
Fan speed status
Low
High
Med
Auto
Quiet
Med-Low Med-High
12
Indoor unit error code
Refer to FGL original error code
13
R.C. prohibition status
Refer to R.C. prohibition setting chart
14
Vertical airflow direction status
1
2
3
4
Swing
15
Horizontal airflow direction status
1
2
3
4
5
Swing
16
Special driving status
Normal
Defrost
Oil
Recovery
17
Managed mode
None
Master
Slave
External
MO
10
Operation mode setting
Cool
Heat
Fan
Dry
Auto
11
Fan speed setting
Low
High
Med
Auto
Quiet
Med-Low Med-High
12
R.C. prohibition setting
Refer to R.C. prohibition setting chart
13
Vertical airflow direction setting
1
2
3
4
Swing
14
Horizontal airflow direction setting
1
2
3
4
5
Swing
TL
10
ECA *1 operation data log
*1) ECA: Electricity Charge Apportionment.
- (05 - 162) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...