2-24. ELECTRICITY CHARGE APPORTIONMENT SETTING
(SYSTEM CONTROLLER, TOUCH PANEL CONTROLLER)
In this section, an electricity charge apportionment function which uses electricity meters is
explained. System Controller (UTY-APGXZ1, UTY-PEGXZ1) or System Controller Lite (UTY-
ALGXZ1, UTY-PLGXA2) or Touch panel controller (UTY-DTGYZ1, UTY-PTGXA) is required to
perform these functions.
ELECTRICITY CHARGE APPORTIONMENT AND ELECTRICITY
METER
When implementing the electricity charge apportionment function in a VRF System, a
configuration which does not use electricity meters or a configuration which uses electricity
meters can be selected. The differences between these two configurations are explained
below.
The electricity charge apportionment function apportions the Input Power to each block
(tenant indoor unit) defined in advance according to the usage record, after the Input Power
(electricity charge) of the air conditioners is input to the System Controller. Electricity charge
apportionment calculation becomes possible only after inputting the Input Power (or electricity
charge).
[Electricity charge apportionment when electricity meter not used]
Only after the electricity bill is received from the electric power company and the billed amount
is input into the System Controller, can electricity charge apportionment for the billed period be
calculated.
[Electricity charge apportionment when electricity meter used]
Since the Input Power data is sent from the electricity meter to the System Controller at any
time, electricity charge apportionment calculation can be performed at any time. Because the
System Controller calculates the energy charge on a daily basis, it can be performed at any
time.
Example (1)
When the tenants are billed for their air conditioning electricity charge once a month and the
electricity bill arrives from the electric power company each month, the electricity charge
apportionment function can be used without electricity meters. Because electricity charge
apportionment can be performed based on that bill. Even if there are tenants moving in and
out within a month, appropriate billing can be performed after the bill was received from the
electric power company. When the electricity bill is received from the electric power company
once every 3 months, the building owner can only bill the building tenants for air conditioning
electricity charges every 3 months. However, if electricity meters are installed, billing at an
arbitrary interval, for example, once a month, is possible.
Example (2)
When air conditioning electricity charge is billed based on the electricity charge apportionment
function for each room in a hotel etc., because guests leave and arrive daily, the electricity
charge is calculated each time they leave. Therefore, you cannot wait for the electricity bill to
arrive from the electric power company. In such cases, an electricity meter must be used to
calculate electricity charge apportionment.
- (07 - 154) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...