CAUTION
●
Before activating the Automatic Address Setting function, be sure to finish setting the refrigerant
circuit addresses of outdoor units.
●
Setting the addresses of indoor units automatically does not necessary mean that addresses are
assigned sequentially starting from the indoor unit which is located the closest to the outdoor units
(instead, addresses are assigned randomly).
With respect to the setting of refrigerant circuit addresses, the same address numbers of the
refrigerant circuit addresses of the outdoor units being connected within the same refrigerant
system are assigned.
●
To find out what addresses have been assigned to individual indoor units, it is necessary to
perform a separate address check operation.
●
When setting addresses of signal amplifiers, indoor units and RB units automatically, be sure to
always set the addresses of signal amplifiers first, set the addresses of indoor units second, set
the addresses of RB units last.
●
Be sure to finish address setting of outdoor unit and indoor unit before performing the automatic
address setting of RB unit.
¾
1: If the total wiring length within a segment is expected to exceed 1,640 ft. (500 m), insert a signal amplifier (Refer to
Chapter 5.).
¾
2: If the number of nodes (the number of units of indoor units, outdoor units, controllers and others) is expected to
exceed 64 (including signal amplifiers), insert a signal amplifier (Refer to Chapter 5.).
- (07 - 53) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...