-1:
Economizer 1 (Cooling 1 occupied)
In / Out Mode 2 or 8 (60-02 or 08)
Function setting
Mode
External output
Remote controller
60-02, 08
2, 8
CNB01
(PIN 1-2)
[Cooling
thermostat
ON]
CNB01
(PIN 1-4)
[Remote
controller
output]
UTY-RNRU
Occupied/Unoccupied
status
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
Menu
Status
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
Wired remote controller
Economizer logic module
Indoor unit
Cooling thermostat ON
(Cooling 1 and Cooling 2) *2
Occupied / Unoccupied status *1
Remote controller output
(Occupied / Unoccupied status)
*1. By the Wired remote controller (Touch panel), external output indication is transferred to Economizer logic mod-
ule through the indoor unit.
*2.Branches the output to Economizer logic module, and connect to Cooling 1 and Cooling 2.
●
Economizer Logic module is required for Economizer operation.
●
Economizer Logic module judges the amount of outdoor air intake depending on indoor unit output of operating
condition, occupied status and outdoor temperature etc.
Operating Mode
Operation
Condition
(Enthalpy or Temp.)
Indoor unit output
Indoor unit
Input
Outdoor air
intake*3
VRF
Indoor unit
Damper
(Free
Cooling)
Outdoor
Return
Cooling
Thermostat
ON
Cooling
High/Low
Occ/Unocc
(RC output)
VRF
Cooling ON
Mechanical
Cooling
Cooling ON
OFF
High
Low
ON
-
ON(Occ)
-
Minimum
Mechanical & Free
Cooling
Cooling ON
ON
Low
High
ON
-
ON(Occ)
-
Modulating
(Min-Max)
Cooling
Thermostat
OFF or Heating
Cooling
OFF
OFF
-
-
OFF
-
ON(Occ)
-
Minimum
OFF
Cooling
OFF
OFF
-
-
OFF
-
OFF(Unocc)
-
None
*3. : When external output by remote controller is OFF, the amount of intaken fresh air differs as follows:
- Cooling by intaken fresh air is performed: None to Maximum amount
- Cooling by intaken fresh air is not performed: None
- (08 - 28) -
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...