[Installation precautions]
Contents
Countermeasures (Reference)
When inside
the ceiling
is high
temperature
and high
humidity
When the indoor unit is installed where the
inside of the ceiling is 86°F (30°C) RH80%
or greater, the dew point temperature of the
outer perimeter may become higher than the
cabinet surface temperature and moisture will
condense on the surface of the cabinet and
water drops may fall inside the room.
→Refer to Fig.A
In addition, the humidity may vary
considerably the same as when the inside of
the ceiling is close to hermetically sealed and
used as the outside air intake path.
1) Add heat insulating material
to the outside of the indoor
unit cabinet.
*Regarding the cassette type,
use of the “high humidity
correspondence kit (option)”
is recommended.
2) Strengthen the heat
insulating material of the
refrigerant piping and drain
piping also.
→Refer to Fig.B
3) When the humidity inside
the ceiling changes
considerably, install a
ventilation port.
Contents
Countermeasures (Reference)
When using
an external
duct
When using an external duct to take in new
fresh air, etc., condensation may form on
the surface of the duct due to the effect of
the outside air temperature and the humidity
inside the ceiling.
1) Always perform heat
insulation processing.
(Heat insulating material:
Glass wool 31/32in (25mm)
thick or more.)
When the
remote
controller
installation site
is bad
If the cold or warm air blown out from the air
conditioner directly contacts the thermostat
section of the remote controller, the outlet
temperature of the air conditioner may be
sensed and room temperature control will be
different from the room temperature and “not
cooled” or “not heated” or other trouble may
occur.
In addition, there is the possibility that the
same kind of trouble may also occur when the
remote controller is effected by direct sunlight.
1) Install the remote controller
where it will not be directly
exposed to the cold or hot
air.
2) Install the remote controller
where it will not be directly
exposed to sunlight or
strong lighting.
Moist air curve
Condition which
requires addition of
outside heat insulation
Relative humidity 80%
Dry bulb temperature 86°F (30°C)
Fig.A
Work method when reinforcing the heat insulation
of on-site piping
Fig.B
Slit of heat insulating
material facing upward
Covered gas pipe
(heat insulation
strengthened)
Heat insulating material
(procured at the site)
Small exposed part of
copper pipe is desirable.
Fit tightly (purpose is
to cover the sealant)
Binding material
Flare connection
To indoor unit
Heat insulation
reinforcement material
(procured at the site)
- (09-05) -
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...