1-4. CONTROL SYSTEM FEATURES
SIMPLE WIRING SYSTEM
● A single transmission line can connect equipment across multiple refrigerant circuits.
● Non polar 2-conductor transmission cable.
● Central control equipment can be connected anywhere on the transmission line, it is not
necessary to connect the indoor units to each outdoor unit.
-Simplifies network installation and start-up
-Reduces the total wiring required
-Helps prevent improper wiring
-Reduces total installation time
LARGE BUILDING APPLICATIONS
● A single VRF network can control an entire building using:
- Total transmission wiring length can be extended up to 11,811 ft. (3,600 m). (with signal
amplifier unit.)
-Up to 400 indoor units per group
-Up to 100 outdoor units per group
-Touch Panel Controller can be used for primary central control.
-Multiple Touch Panel Controllers may be sued to provide convenient control for multiple
convertor (Refer to 3-1.)
- Can control Fujitsu mini-split and HFI models using a Network Convertor (Refer to 3-1.)
● System Controller allows to control up to 4 VRF network systems (Max.1,600 indoor units),
suitable for huge scale application.
RELIABILITY AND EASE OF MAINTENANCE
● Stand-alone transmission NETWORK allows for each unit to operate separately; therefore,
an error at one unit does not effect the performance of the remaining units.
● When a failure occurs, the error code is displayed on the individual controller and central
controller. (except Wireless Remote Controller)
● Error history is stored in each individual controller and in the central controller (except
wireless controller).
● System Controller and Web Monitoring Tool allow to monitor operation status in real time via
INTERNET, allowing for a quick evaluation of VRF systems.
● Service tool can connect anywhere on the transmission line, allowing building owner to
quickly evaluate the performance of the VRF system.
- (05 - 10) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...