Function
Function
number
Setting number
Default
Details
*1 Auto
restart
40
00
Enable
Enable or disable automatic system restart after a power outage.
01
Disable
Cool Air
Prevention
43
00
Super low
Restrain the cold airflow with making the airflow lower when starting
heating operation. To correspond to the ventilation, set to 01.
01
Follow the setting
on the remote
controller
External
control
46
00
Start/Stop
Allow an external controller to start or stop the system, or to perform
an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01
Emergency stop
02
Forced stop
Error
report
target
47
00
All
Change the target for reporting errors. Errors can either be reported in
all locations, or only on the wired remote.
01
Display only on
central remote
control
Fan setting
when cooling
thermostat OFF
49
00
Follow the setting
on the remote
controller
When set 00, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
changed Fan mode forcibly.
When set 01, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
stop forcibly.
Connection of the wired remote controller
(2-wire type or 3-wire type) and switching its thermistor are necessary.
01
Stop
*2 Switching
functions
for external
inputs and
external outputs
terminals
60
00
Mode 0
Set this function when connected to external devices such as the VRF
system ventilator, economizer, humidifier, etc.
The connection terminal functions can be changed depending on
the type of external device. For details of the connection terminal
functions, refer to Chapter 8. 1-2. INDOOR UNIT.
01
Mode 1
02
Mode 2
03
Mode 3
04
Mode 4
05
Mode 5
06
Mode 6
07
Mode 7
08
Mode 8
Control
switching of
external heaters
61
00
Auxiliary heater
control 1
Sets the control method for the external heater being used. For details
of the control method, refer Chapter 8.
1-2-2. EXTERNAL OUTPUT.
01
Auxiliary heater
control 2
02
Heat pump
prohibition control
03
*3
Heater selection
control using
external
temperature 1
04
*3
Heater selection
control using
external
temperature 2
Operating
temperature
switching of
external heaters
62
00
Setting 0
Sets the temperature conditions when the external heater is ON.
For the temperature conditions, see "Temperature conditions when the
external heater is ON".
01
Setting 1
02
Setting 2
03
Setting 3
04
Setting 4
05
Setting 5
*1 : Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2 : Inappropriate setting may cause an external device malfunction. Confirm whether all the settings have been
performed appropriately according to the installing condition.
*3 : Only VR-II is setable.
- (07 - 113) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...