1-2. CHECKING CONCENTRATION LIMIT
Check concentration limit following steps
, and take appropriate measures depending on
the situation.
Calculate amount of refrigerant [lbs. (kg)] per refrigerant system.
Smallest room volume.
Calculate room volume by regarding
portion as one room or the smallest room.
Calculate refrigerant concentration from the results of
and
Amount of refrigerant per
refrigerant system
Amount of additional
refrigerant
Total amount of refrigerant in
system (lbs, kg)
+
=
Amount of factory
charged refrigerant
Amount of refrigerant
added to system based
on pipe length, pipe size
and indoor units.
Note : When one refrigerant
system is divided into 2 or more
refrigerant systems and each
system is independent, total
amount of refrigerant of each
system shall be adopted.
Total amount of refrigerant in
refrigerant system (lbs,kg)
When the result of calculation
exceeds the limiting
concentration,perform the same
calculations by shifting to the
second smallest,and the third
smallest rooms until the final result
is below the limiting concentration.
≤ Refrigerant concentration [lbs./Mcf
(kg/m
3
)]
(R410A)
Capacity of smallest
room where indoor unit is
installed [cf (m
3
)]
(a) Without partition
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Smallest
room
Indoor unit
Partition
Opening
(b) When there are partitions,
but there is an effective
opening for ventilation between
the rooms.
(c) With partition and without
opening which serve as
passage of air to adjoining
room.
- (09-02) -
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...