46
Code
OLED
Display
Name
Basic
Supply
Fan
Exhaust
Fan
Cooling
Tower
Surface/
Booster
Pump
23
Hand
Run
Cmd
0
‐
HOA
in
Hand
0
‐
HOA
in
Hand
0
‐
HOA
in
Hand
0
‐
HOA
in
Hand
0
‐
HOA
in
Hand
24
Hand
Speed
Ref
0
‐
Keypad
0
‐
Keypad
0
‐
Keypad
0
‐
Keypad
0
‐
Keypad
30
Stop
Mode
1(Coast)
1(Coast)
1(Coast)
1(Coast)
1(Coast)
31
Stop
Mode
10
[Hz]
10
[Hz]
10
[Hz]
10
[Hz]
10
[Hz]
32
DC
Braking
Start
Frequency
50
[%]
50
[%]
50
[%]
50
[%]
50
[%]
33
DC
Braking
Current
5.0
[sec]
5.0
[sec]
5.0
[sec]
5.0
[sec]
5.0
[sec]
34
Acceleration
Time
30.0
[sec]
30.0
[sec]
30.0
[sec]
30.0
[sec]
20.0
[sec]
35
Deceleration
Time
40.0
[sec]
40.0
[sec]
40.0
[sec]
40.0
[sec]
30.0
[sec]
36
V/F
Control
0
(Linear)
1
(Squared)
1
(Squared)
1
(Squared)
0
(Linear)
39
Speed
‐
Search
Voltage
Gain
100%
100%
100%
100%
100%
40
Speed
‐
Search
Speed
Offset
5.0
[Hz]
5.0
[Hz]
5.0
[Hz]
5.0
[Hz]
5.0
[Hz]
41
Auto
Run
Cmd
(1)
Terminal
(1)
Terminal
(1)
Terminal
(1)
Terminal
(1)
Terminal
42
Auto
Speed
Ref
(1)
1A
Input
(4)
PID
(4)
PID
(4)
PID
(4)
PID
43
Anlg
Ref
Loss
(0)
Disabled
(1)
Half
of
Min
(1)
Half
of
Min
(1)
Half
of
Min
(1)
Half
of
Min
44
Anlg
Ref
Loss
Act
(0)
Fault
(1)
Stop
(1)
Stop
(2)
Hold
(1)
Stop
45
Anlg
Ref
Loss
1
[Sec]
1
[Sec]
1
[Sec]
1
[Sec]
1
[Sec]
46
PID
Mode
(0)
Direct
(0)
Direct
(1)
Inverse
(1)
Inverse
(0)
Direct
47
Setpoint
Source
(0)
Keypad
(0)
Keypad
(0)
Keypad
(0)
Keypad
(0)
Keypad
48
Feedback
Source
(0)
1A
Input
(0)
1A
Input
(0)
1A
Input
(0)
1A
Input
(0)
1A
Input
49
Feedback
Units
(0)
PSI
(2)
inWC
(2)
inWC
(6)
°F
(0)
PSI
50
Feedback
Max
100.00
[PSI]
10.00
[inWC]
10.00
[inWC]
150.00
[°F]
100.00
[PSI]
52
Keypad
Setpoint
60.00
[PSI]
1.00
[inWC]
1.00
[inWC]
78.00
[°F]
60.00
[PSI]
55
P
Gain
30
[%]
10
[%]
10
[%]
10
[%]
30
[%]
56
I
Gain
1.0
[sec]
1.0
[sec]
1.0
[sec]
1.0
[sec]
0.5
[sec]
57
PID
Ramp
Time
0.0
[sec]
0.0
[sec]
0.0
[sec]
0.0
[sec]
0.0
[sec]
58
PID
High
Freq
Limit
60.00
[Hz]
60.00
[Hz]
60.00
[Hz]
60.00
[Hz]
60.00
[Hz]
59
PID
Low
Freq
Limit
20.00
[Hz]
15.00
[Hz]
15.00
[Hz]
15.00
[Hz]
20.00
[Hz]
60
Fdbk
Loss
(1)
Half
of
Min
(1)
Half
of
Min
(1)
Half
of
Min
(1)
Half
of
Min
(1)
Half
of
Min
61
Fdbk
Loss
Action
(1)
Stop
(1)
Stop
(1)
Stop
(2)
Hold
(1)
Stop
62
Fdbk
Loss
Delay
1
[Sec]
1
[Sec]
1
[Sec]
1
[Sec]
1
[Sec]
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...