PROT-9: Bypass MOL Class
Bypass MOL Class
9) 10
0 - Class 5
1 - Class 6 (Pump)
2 - Class 10
3 - Class 20
Default: (2) 10
Motor
overload
industry
standard
class
curve
selections.
(ONLY
for
VFD)
PROT-12: Overcurrent Level
Overcurrent Level
12) 200%
Min: 70%
Max: 200%
Default: 200%
%
of
motor
FLA.
If
any
phase
current
is
greater
than
setting
for
MOC
delay,
VFD
trips.
This
level
as
a
percentage
of
Motor
FLA
determines
a
fault
trigger
point.
If
motor
current
exceeds
this
level
for
PROT
‐
13
Delay
time,
the
VFD
trips
on
Motor
Overcurrent
(MOC).
This
is
a
safeguard
from
running
the
motor
with
windings
or
motor
leads
electrical
failure.
PROT-13: Overcurrent Delay
Overcurrent Delay
13) 0.1s
Min: 0.1s
Max: 5.0s
Default: 0.1s
Delay
before
Motor
Overcurrent
Fault
occurs.
Sets
the
delay
time
for
the
Motor
Overload
trip.
Timer
starts
when
the
current
exceeds
PROT
‐
12
level.
Timer
will
be
reset
if
counting
during
Motor
Overload
Current
Condition
and
the
current
drops
below
the
Motor
Overload
Current
Level.
PROT-38: Critical Fault Retries
Crit Fault Retries
38) 3
Min: 0
Max: 10
Default: 3
Sets
number
of
retry
attempts.
0
=
disabled.
PROT-39: Critical Fault Retry Delay
Crit Fault Retry Delay
39) 180s
Min: 0s
Max: 6000s
Default: 180s
Sets
time
delay
before
retry
attempts.
Available
when
PRIMARY
‐
18
is
greater
than
0
PROT-40: Normal Fault Retries
Nrml Fault Retries
40) 3
Min: 0
Max: 10
Default: 3
Sets
number
of
retry
attempts.
0
=
disabled.
PROT-41: Normal Fault Retry Delay
Nrml Fault Retry Delay
41) 120s
Min: 0s
Max: 6000s
Default: 120s
Sets
time
delay
before
retry
attempts.
Available
when
PRIMARY
‐
18
is
greater
than
0.
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...