CHAPTER 8 – PARAMETER DESCRIPTIONS
CHAPTER 8 - PARAMETER DESCRIPTIONS
8.2
Primary – Basic Setup Group
PRIMARY
PARAMETERS
PRIMARY-1: Application Selection
Application
1)
BASIC
Default: Basic
0 - Basic
1 - Supply Fan
2 - Exhaust Fan
3 - Cooling Tower
4 - Surface/Booster
Pump
PRIMARY
‐
1
Sets
parameters
based
on
a
specific
application.
Starter
mode
provides
very
simple
motor
control
at
set
speed
or
at
preset
speeds
by
digital
inputs.
The
first
step
in
VFD
setup
is
an
application
selection.
There
are
six
application
choices:
Basic,
Supply
Fan,
Exhaust
Fan,
Cooling
Tower
Fan,
Centrifugal
Pump
and
Starter.
The
Basic
selection
provides
a
standard
basic
VFD
control
with
start/stop
command
from
keypad
and
mobile
app
interface.
The
Supply
or
Exhaust
Fan
selection
sets
VFD
for
remote
BMS
(Building
Management
System)
or
PLC
(Programmable
Logic
Controller)
Start/Stop
control
and
4
‐
20mA
speed
reference
signal.
All
other
related
parameters
such
as
Transducer
range,
Process
Unit
in
WC,
Direct
or
Inverse
PID,
etc.
will
be
automatically
set
to
the
most
common
factory
default
values
providing
accurate
motor
control.
In
some
cases,
extra
adjustment
of
some
parameters
is
necessary
to
achieve
better
control.
Stop
mode
is
set
to
Coast
mode
to
protect
from
any
possible
overvoltage
trips
while
decelerating
during
stop
mode.
The
Cooling
Tower
Fan
selection
configures
VFD
for
fan
motor
with
internal
inverse
PID
control
and
feedback
from
a
temperature
transducer.
The
process
unit
is
set
to
°F
with
0
‐
150°F
temperature
transducer
range
and
80°F
PID
set
point.
If
MMC
(Multi
‐
Motor
Control)
feature
is
enabled
with
one
of
the
auxiliary
relays,
the
VFD
can
start
a
spray
pump
based
on
VFD
speed
and
system
temperature.
The
inverse
PID
control
increases
fan
motor
speed
if
temperature
is
above
set
point.
The
Surface/Pump
selection
provides
constant
pressure
PID
control
with
pressure
transducer
feedback.
The
process
unit
is
set
to
PSI
with
0
‐
100PSI
transducer
range
and
50PSI
set
‐
point.
The
sleep
mode
is
enabled
and
parameters
are
set
to
optimal
values,
which
should
be
readjusted
for
better
performance
based
on
the
system
parameters
and
type
of
pump
PRIMARY-2: Rated Motor Voltage
Motor Voltage
2) 460V
Min: 200
Max: 480
Default: 460
The
motor
voltage
rating
should
be
checked
on
the
motor
nameplate
and
set
in
PRIMARY
‐
2
parameter.
The
VFD
can
produce
output
voltage
equal
to
or
less
than
input
power
voltage.
PRIMARY-3: Rated Motor Horsepower
Motor Horsepower
3) 5HP
Min: 1
Max: 200
Default: 5
The
HP
rating
from
the
motor
nameplate
should
be
put
in
this
parameter.
If
VFD
temperature
rating
needs
to
be
increased
up
to
122°F,
de
‐
rate
this
parameter
by
20%.
The
kW
rating
is
for
230V
or
415V
motor
with
FLA
close
to
UL
table
for
corresponding
HP
rating.
PRIMARY-4: Rated Motor Current
Motor Current
4) 0.5A
Min: 0.5
Max: 55.0
Default: 0.5
The
Motor
Current
will
automatically
detect
and
adjust
according
to
DC
bus
voltage,
Line
Frequency
and
VFD
size
during
initial
power
‐
up.
The
PRIMARY
‐
4
parameter
can
be
changed
to
the
motor
nameplate
FLA
if
different
from
default.
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...