112
Multi
‐
State
Objects:
BACnet
Object
Instance
Read/
Write
Full
Parameter
Name
OLED
Display
Name
Units
Parameter
Setting
Range
0
R/W
Application
Application
x
0
‐
Basic
1
‐
Supply
Fan
2
‐
Exhaust
Fan
3
‐
Cooling
Twr
4
‐
Surface/Booster
Pump
1
R/W
Power
Line
Frequency
Line
Frequency
x
0
‐
50
[Hz]
1
‐
60
[Hz]
2
R/W
Power
‐
On
Run
Power
‐
On
Run
x
0
‐
Disable
1
‐
Enable
3
R/W
Run
after
Fault
Reset
Fault
Reset
&
Run
x
0
‐
Disable
1
‐
Enable
4
R/W
Start
Mode
Start
Mode
x
0
‐
Accelerate
1
‐
DC
Start
2
‐
Flying
Start
5
R/W
DC
Start
Level
*
DC
Start
Level
x
0
‐
Low
1
‐
Medium
2
‐
High
6
R/W
HOA
Type
HOA
Type
x
0
‐
Keypad
HOA
1
‐
Auto
Only
2
‐
Keypad
Off/Auto
3
‐
External
HOA
7
R
HOA
Status
HOA
Mode
x
0
‐
Off
1
‐
Hand
2
‐
Auto
3
‐
Bluetooth
8
R/W
Run
Command
in
Hand
Hand
Run
Cmd
x
0
‐
HOA
in
Hand
1
‐
Terminal
2
‐
3
‐
Wire
3
‐
Comms
9
R/W
Speed
Reference
in
Hand
Hand
Speed
Ref
x
0
‐
Keypad
1
‐
1A
Analog
Input
2
‐
2A
Analog
Input
3
‐
Communications
4
‐
3A
Analog
Input
10
R/W
Stop
Mode
Stop
Mode
x
0
‐
Decel
1
‐
Coast
2
‐
DC
Brake
11
R/W
V/F
Control
Mode
V/F
Control
x
0
‐
Linear
1
‐
Squared
12
R/W
Run
Command
in
Auto
Auto
Run
Cmd
x
0
‐
HOA
in
Auto
1
‐
Terminal
2
‐
3
‐
Wire
3
‐
Comms
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...