82
I/O-24: 2A Input Min V
2A Input Min V
24) 0V
Min: 0.0V
Max: 10.0V
Default: 0.0V
2A
Voltage
Input
minimum
value.
For
2
‐
10VDC
signal
set
it
to
2V
I/O-25: 2A Input Min Hz
2A Input Min Hz
25) 0Hz
Min: 0.00 Hz
Max: PRIMARY-7
Default: 0.00 Hz
2A
Voltage
Input
maximum
value.
For
0
‐
5VDC
signal
set
it
to
5V
I/O-26: 2A Input Max V
2A Input Max V
26) 10V
Min: 0.0V
Max: 10.0V
Default: 10.0V
2A
Voltage
Input
frequency
corresponding
to
V
Min
I/O-27: 2A Input Max Hz
2A Input Max Hz
27) 60Hz
Min: 0.00
Max: PRIMARY-7
Default: 60.00 Hz
2A
Voltage
Input
frequency
corresponding
to
V
Max
I/O-28: 2A Output Function
2A Function
28) Output Frequency
Default: Out. Freq.
0 - Output Frequency
1 - Output Current
2 - DC Bus Voltage
3 - Repeat 1A*
4- Repeat 3A*
2A
Analog
Output
(0
‐
10V
or
4
‐
20mA
set
by
DIP
Switch)
parameter
selection.
Analog
output
is
scaled
to
Max
value
of
the
selected
parameter.
Example:
DC
Link
Voltage
is
0
‐
1000VDC.
I/O-29: 2A Output Scaling
2A Output Scaling
29) 100%
Min: 10%
Max: 200%
Default: 100%
2A
Analog
output
scaling.
For
max
Frequency
60Hz
at
50%
setting,
2A
output
will
provide
5VDC
or
12mA
(depending
on
2A
DIP
Sw
position).
I/O-48: Option Board Enable
Option Board
48) Enabled
0 - Disable
1 – Enable
Default: Enabled
I/O-49: Dry Input 3 Function
D3-SG Function
49) None
0 - None
1 - Enable
2 - Fireman's Override
3 - Speed- A
4 - Speed- B
5 - Setpoint-A
6 - Setpoint-B
7 - Damper LSW (H)
8 - Reserved
9 - External Trip
10 - Reserved
11 - Reserved
12 - 2nd Acc/Dec Time
13 - 3-Wire Start
14 - 3-Wire Stop
15 - HOA Auto
16 - HOA Hand
17 - Shutdown
18- Fault Reset
19- Bypass
20- Reserved
Default: None
I/O-50: Dry Input 3 Contact
D3-SG Input
50) N.O.
0 – Normally Open
1 – Normally Closed
Default: N.O.
I/O-51: Dry Input 3 Contact
D3-SG Function
51) None
0 - None
1 - Enable
2 - Fireman's Override
3 - Speed- A
4 - Speed- B
5 - Setpoint-A
6 - Setpoint-B
7 - Damper LSW (H)
8 - Reserved
9 - External Trip
10 - Reserved
11 - Reserved
12 - 2nd Acc/Dec Time
13 - 3-Wire Start
14 - 3-Wire Stop
15 - HOA Auto
16 - HOA Hand
17 - Shutdown
18- Fault Reset
19- Bypass
20- Reserved
Default: None
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...