99
Fault
Cause
Remedy
Ground
Fault
(L)
Occurs
when:
Ground
fault
current
exceeds
the
internal
ground
fault
level
value.
Ensure
Motor
and
VFD
are
grounded
per
the
installation
guide.
Disconnect
motor
wires
from
package
and
Check
the
output
wiring
and
insulation
of
motor
windings
with
Megger
tester.
Bypass
Motor
Overload
The
Bypass
Motor
Overload
protection
provides
motor
overload
protection
when
in
Bypass
mode
only.
If
the
motor
pulls
more
current
than
set
motor
FLA,
it
will
trip
based
on
selected
trip
class
to
prevent
motor
damage.
Check
FLA,
Trip
Class,
Check
if
motor
is
overloaded
Bypass
Phase
Loss
The
bypass
did
not
see
current
in
one
or
more
of
the
phases.
Check
wiring
passing
through
the
bypass
current
sensors
for
loose
connections.
Bypass
Board
Error
The
bypass
board
error
is
a
“hard
fault”
and
requires
that
the
board
be
power
cycled
to
clear
it.
If
Power
cycle
does
not
clear
the
fault,
please
consult
factory
Bypass
Stall
The
Stall
fault
occurs
when
the
current
exceeds
300%
of
set
FLA
for
0.5
sec
and
the
current
slope
is
not
decreasing.
(Not
active
during
startup).
Check
FLA
settings.
Check
if
motor
is
overloaded.
Check
for
mechanical
issues
(bad
bearings,
bad
gears
or
belts)
If
nothing
helps
Adjust
stall
level
higher.
(Default
is
300%)
Bypass
Max
Time
to
Start
A
max
time
to
start
trip
occurs
if
the
motor
current
has
not
decreased
below
FLA
10
seconds
after
start.
Check
that
your
FLA
setting
in
PRIMARY
‐
04
matches
the
motor
nameplate
Check
the
motor
and
system
for
mechanical
issues
Check
your
dip
switch
settings
Check
power
wiring
for
loose
connection.
Bypass
Ground
Fault
A
Ground
Fault
occurs
when
bypass
module
determines
that
there
is
a
motor
ground
leak
current.
Disconnect
motor
leads
from
bypass
package
and
test
insulation
with
Megger
If
Megger
reading
shows
low
insulation,
check
motor
wiring
and
motor
junction
box
for
damaged
wire
insulation
and
moisture
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...