31
4.8
Digital and Analog Control Circuit Terminal Layout
Description
Name
Type
Description
Details
Damper
Output
A+
Terminal
24VDC
Damper
out
V+
(positive)
24VDC
Damper
supply,
0.5A
max
A
‐
Terminal
24VDC
Damper
out
V
‐
(negative)
Analog
In/Out
24
Terminal
24VDC
Control
Power
Output
24VDC
supply
capable
of
50mA
maximum.
Analog
PID
reference
or
speed
reference.
Max
Error
allowed
is
1%
of
Full
Scale
1A
Terminal
Input
(0
‐
10V
/
0
‐
24V
/
4
‐
20mA)
2A
Terminal
Configurable
Input
/
Output
0
‐
10V
SG
Terminal
Signal
Ground
Dry
Input
Terminals
D1
Terminal
Dry
Input
1
default:
Run/N.O.
Shutdown
/
Permissive
/
Fireman's
Override
/
Limit
Switch
/
Speed
A
/
Speed
B
/
None
‐
SW
configurable
Internal
24VDC
3mA
circuit.
D2
Terminal
Dry
Input
2
default:
None/N.O.
SG
Terminal
Signal
ground/Shield
Communications
CG
Terminal
Communications
Ground
RS
‐
485
port
for
Modbus
RTU
and
BACnet
MS/TP
Communications
‐
Terminal
‐
RS
‐
485
+
Terminal
+RS
‐
485
SG
Terminal
Signal
Ground/Shield
Wiring
for
communication
to
multiple
drives
M
‐
Terminal
‐
RS
‐
485
M+
Terminal
+
RS
‐
485
E1
CAT5
Ethernet
Port
Comm
Port
for
Modbus
IP
and
BACnet
IP
(Not
pictured
above
–
located
below
HOA
buttons,
on
the
left
of
the
cooling
fan
cover)
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...