background image

121 

 

BACnet

 

Object

 

Instance

 

Read/

 

Write

 

Full

 

Parameter

 

Name

 

OLED

 

Display

 

Name

 

Units

 

Parameter

 

Setting

 

Range

 

93

 

R

  

Bluetooth

 

Error

 

Bluetooth

 

Error

 

x

 

0

 ‐ 

None

 

1

 ‐ 

HW

 

Comms

 

Fail

 

2

 ‐ 

No

 

"Adv

 

Off"

 

Rsp

 

3

 ‐ 

No

 

"Cfg"

 

Response

 

4

 ‐ 

No

 

"Cfg

 

Val"

 

Rsp

 

5

 ‐ 

No

 

"Write"

 

Rsp

 

6

 ‐ 

No

 

"Adv

 

On"

 

Rsp

 

7

 ‐ 

No

 

"LNAME"

 

Rsp

 

8

 ‐ 

No

 

"SNAME"

 

Rsp

 

9

 ‐ 

No

 

"Disconnect"

 

Rsp

 

10

 ‐ 

No

 

"Satus

 

Ok"

 

Rsp

 

11

 ‐ 

No

 

"Version"

 

Rsp

 

12

 ‐ 

No

 

"Transparent"

 

Rsp

 

13

 ‐ 

No

 

"Tx

 

Comp"

 

Rsp

 

14

 ‐ 

Unexpected

 

Reset

 

15

 ‐ 

Unexpected

 

Element

 

16

 ‐ 

Invalid

 

Firmware

 

17

 ‐ 

No

 

"Exit

 

Trans"

 

Rsp

 

18

 ‐ 

Procedure

 

Overrun

 

19

 ‐ 

Not

 

In

 

Trans

 

Mode

 

20

 ‐ 

No

 

"LBD"

 

Response

 

21

 ‐ 

No

 

"DCN"

 

Response

 

22

 ‐ 

FW

 

Upgrade

 

Failure

 

 
 

 

Summary of Contents for Q-link

Page 1: ...ation Contact the nearest authorized service facility for examination repair or adjustment Do not disassemble or repair unit death or injury due to electrical shock or fire hazard may result Product i...

Page 2: ...your equipment is as follows This is the safety alert symbol Read and follow instructions carefully to avoid a dangerous situation This symbol alerts the user to the presence of dangerous voltage insi...

Page 3: ...herwise electric shock could occur Install VFD on a non flammable surface Do not place flammable materials nearby Otherwise fire could occur Disconnect the input power if VFD has been damaged Otherwis...

Page 4: ...ult in VFD and or equipment damage Reversing the polarity of the digital control terminals can damage VFD Perform wiring after VFD has been mounted Otherwise electric shock or bodily injury can occur...

Page 5: ...les with paralleled wires will increase the amplitude of these spikes at motor terminals Install output reactor or filter to protect motor winding insulation based on distance range from VFD to a moto...

Page 6: ...3 10 COMMON SPECIFICATIONS 20 3 11 I O SPECIFICATIONS 21 3 12 ENVIRONMENT 21 3 13 CERTIFICATION 22 CHAPTER 4 INSTALLATION AND WIRING 23 4 1 INSTALLATION AND PRECAUTIONS 23 4 2 CONDUIT GUIDELINES 25 4...

Page 7: ...IONS 69 8 2 PRIMARY BASIC SETUP GROUP 69 8 3 VFD ADVANCED SETUP GROUP 77 8 4 I O TERMINALS 80 8 5 PROTECTION 84 8 6 COMMUNICATION 86 8 7 VIEW INFORMATION 88 8 8 FAULT CODES 91 8 9 ADMINISTRATION 94 CH...

Page 8: ...D display with an easy to use control interface and onboard navigation menu Q Link s iOS and Android applications interface affords secure Bluetooth connectivity for the added convenience of device mo...

Page 9: ...9 1 2 Q Link VFD Models Q Link Base Drive Current rated stand alone VFD Q Link Smart Bypass Current rated drive with integrated smart bypass...

Page 10: ...10 Q Link Drive with Disconnect Current rated drive with integrated disconnect switch Q Link HP Rated Drive HP rated stand alone VFD...

Page 11: ...R 2 BASIC INFORMATION CHAPTER 2 BASIC INFORMATION 2 1 Part Number Code and Initial Inspection 2 1 1 Part Number Anatomy Amperage Rated VFD Base Drive Smart Bypass and Drive with Disconnect Horsepower...

Page 12: ...12 2 1 2 UL Label...

Page 13: ...agent and your FCS Franklin Control Systems sales representative Figure 2 2 1 Remove the VFD cover and inspect VFD for any damage or foreign objects Check VFD part number current rating and nominal vo...

Page 14: ...correctly applied or installed VFD can result in system malfunction or reduction in product life as well as component damage You must read and understand this manual thoroughly before proceeding with...

Page 15: ...15 CHAPTER 3 SPECIFICATIONS CHAPTER 3 SPECIFICATIONS 3 1 Standalone VFD Ratings 3 2 VFD Smart Bypass Ratings...

Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...

Page 17: ...17 3 5 Standalone and HP Rated VFD Torque Ratings 3 6 VFD Smart Bypass Torque Ratings 3 7 VFD Disconnect Torque Ratings...

Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...

Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...

Page 20: ...peration Method OLED display and keypad HOA buttons Terminals Bluetooth mobile app Communications Frequency Setting Keypad Analog Voltage and Current 0 10V 4 20mA Bluetooth mobile app Communications P...

Page 21: ...lectable 1A 2A 3A 1A AI 0 10V 0 24V 4 20mA 2A AIO 0 10V input or 0 10V 4 20mA output 3A AI 4 20mA Mode Voltage or Current Level 0 10VDC or 4 20mA Analog Output Control Power 24VDC 50mA Max Damper Outp...

Page 22: ...cations Certifications Agency Approvals UL cUL Enclosure Rating UL Type 1 Plenum rated UL508C Available packaged as UL Type 12 IP54 UL Type 3R IP54 UL Type 4X IP66 Keypad Rating UL Type 1 IP21 Harmoni...

Page 23: ...D with care to prevent damage to the plastic components Do not hold VFD by the front cover Do not mount VFD on the equipment with excessive vibration above 5 9 m sec2 Install VFD in a location where t...

Page 24: ...ounted inside the appropriate electrical enclosure with proper NEMA UL or IP rating and adequate cooling If VFD is mounted inside an enclosure please consult factory for ambient temperature considerat...

Page 25: ...conduit guidelines as shown in the figure below Refer to Figure 4 2 1 Figure 4 2 1 CAUTION VFD can malfunction or be damaged if motor and power wires are in the same conduit or motor wires from two o...

Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...

Page 27: ...27 4 4 Wiring Schematic Smart Bypass...

Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...

Page 29: ...for multiple VFDs in common conduit See Figure 4 3 1 Do not install power factor correction capacitors surge suppressors or RFI filters on the VFD output These devices can trigger some VFD faults or...

Page 30: ...s are used as ground leak current path the VFD can have inadequate grounding and ground fault protection Connect ground wire first before any other wires and only connect it to the dedicated ground te...

Page 31: ...G Terminal Signal Ground Dry Input Terminals D1 Terminal Dry Input 1 default Run N O Shutdown Permissive Fireman s Override Limit Switch Speed A Speed B None SW configurable Internal 24VDC 3mA circuit...

Page 32: ...A 125VAC Max Switching Voltage 250VAC 04 Terminal Default Selection Fault COM 05 Terminal Default Selection Fault N O Analog Input 1A SG The Analog Input mode is user selectable 0 10V 0 24V or 4 20mA...

Page 33: ...0 Analog DIP Switch Configurations The analog I O configuration DIP switches 1 through 4 can be found to the right of the analog I O terminals DIP switches must be configured per the illustrations bel...

Page 34: ...switches can be found on the upper left of the unit BPC present only in the Q Link Smart Bypass packages The default position for both switches is OFF The BPC module functions can be enabled by movin...

Page 35: ...35 4 12 PID Control Diagram...

Page 36: ...application allows for instant access to VFD 5 Bluetooth Connection Device Pairing Available Indicates that the VFD is capable of supporting a Bluetooth connection 6 Soft Keys These keys correspond t...

Page 37: ...37 5 2 Control Interface...

Page 38: ...ed to a pressure transducer Refer to the parameter table at the end of this quick start for presets Step 2 Enter Rated Motor Voltage Basic 02 Enter the rated voltage of the motor from the motor namepl...

Page 39: ...mode normal operation the right soft key will display Bypass To enter into bypass mode press the bypass button Once in bypass mode the screen will indicate BYP in place of the drive speed as it will n...

Page 40: ...or allows the user to select desired values to monitor see section 5 4 4 below 5 4 4 Configurable Quick Monitor Screen The Configurable Quick Monitor screen displays four horizontal rows The first thr...

Page 41: ...ither Scan QR Code Sticker or Enter an Access Code A QR code targeting screen will appear upon tapping Scan QR Code Sticker Once the QR code is acquired and verified a new VFD item is added to the Loc...

Page 42: ...d Motor Current Motor Current 0 5A to VFD Rating No 5 105 Rated Motor RPM Motor RPM 500 to 3600 RPM No 6 106 Power Line Frequency Line Frequency 0 50 Hz 1 60 Hz No 7 107 Maximum Frequency Max Frequenc...

Page 43: ...re 3 Comms No 24 124 Speed Reference in Hand Hand Speed Ref 0 Keypad 1 1A Analog Input 2 2A Analog Input 3 Communications 4 3A Analog Input No 30 130 Stop Mode Stop Mode 0 Decel 1 Coast No 31 131 DC B...

Page 44: ...urce 0 1A Input 1 2A Input 2 3A Input No 49 149 PID Feedback Unit Feedback Units 0 PSI 0 1 1 GPM 0 1 2 inWC 0 01 3 CFM 0 1 4 inHg 0 1 5 Feet 0 1 6 F 0 1 7 mBar 0 01 8 Pa 0 1 9 kPa 0 01 10 Meters 0 1 1...

Page 45: ...Rating By UL Table by Line Hz Voltage and VFD Rating 5 Motor RPM 1750 RPM 1750 RPM 1750 RPM 1750 RPM 1750 RPM 6 Line Frequency 1 60 Hz 1 60 Hz 1 60 Hz 1 60 Hz 1 60 Hz 7 Max Frequency 60 00 Hz 60 00 Hz...

Page 46: ...t 4 PID 4 PID 4 PID 4 PID 43 Anlg Ref Loss 0 Disabled 1 Half of Min 1 Half of Min 1 Half of Min 1 Half of Min 44 Anlg Ref Loss Act 0 Fault 1 Stop 1 Stop 2 Hold 1 Stop 45 Anlg Ref Loss 1 Sec 1 Sec 1 Se...

Page 47: ...sabled 1 Enabled No 14 214 Skip Frequency 2 Low Skip Freq 2 Low 0 50 to Skip 2 High Hz Yes 15 215 Skip Frequency 2 High Skip Freq 2 High Skip 2 Low Hz to VFD Max Hz Yes 16 216 Skip Frequency 3 Selecti...

Page 48: ...y Usage 3 Average Power 4 Average Current 5 Line A Current 6 Line B Current 7 Line C Current 8 DC Bus Voltage 9 Output Voltage 10 HOA Mode 11 IGBT Temp 12 Ambient Temp 13 Motor Run Time 14 D1 SG Input...

Page 49: ...ble 0 Disabled 0 Disabled 0 Disabled 0 Disabled 0 Disabled 14 Skip Freq 2 Low 33 00 Hz 33 00 Hz 33 00 Hz 33 00 Hz 33 00 Hz 15 Skip Freq 2 High 36 00 Hz 36 00 Hz 36 00 Hz 36 00 Hz 36 00 Hz 16 Skip Freq...

Page 50: ...3 Wire Start 14 3 Wire Stop 15 HOA Auto 16 HOA Hand 17 Shutdown 18 Fault Reset 19 Bypass No 2 302 Dry Input 1 Contact D1 SG Input 0 Normally Open 1 Normally Closed No 3 303 Dry Input 2 Function D2 SG...

Page 51: ...Start 14 3 Wire Stop 15 HOA Auto 16 HOA Hand 17 Shutdown 18 Fault Reset 19 Bypass No 6 306 Wet Input 1 Type V1 V2 Input 0 Active High 1 Active Low No 7 307 Wet Input 2 Function V3 V4 Function 0 None 1...

Page 52: ...vel 1A Input Filter 0 Low 1 Medium 2 High Yes 19 319 1A V Min Value 1A Input Min V 0 00 to 10 00 V No 21 321 1A V Max Value 1AInput Max V 0 00 to 10 00 V No 23 323 2A V Input Filtering Level 2A Input...

Page 53: ...Reserved 13 3 Wire Start 14 3 Wire Stop 15 HOA Auto 16 HOA Hand 17 Shutdown 18 Fault Reset 19 Bypass 20 Reserved 50 350 Dry Input 3 Contact D3 SG Input 0 Normally Open 1 Normally Closed 51 351 Dry In...

Page 54: ...53 353 Relay 3 Output Select O3 O4 O5 Function 0 Fault 1 Run 2 Proof of Run Yes 64 364 3A mA Min Value 3A Input Min mA 0 00 to 20 00 mA No 65 365 3A Min Hz 3A Min Hz 0 00 to Prime 07 Hz No 66 366 3A...

Page 55: ...00 mA 4 00 mA 15 1A Min Hz 0 00 Hz 0 00 Hz 0 00 Hz 0 00 Hz 0 00 Hz 16 1A Input Max mA 20 00 mA 20 00 mA 20 00 mA 20 00 mA 20 00 mA 17 1A Max Hz 60 00 Hz 60 00 Hz 60 00 Hz 60 00 Hz 60 00 Hz 18 1A Inpu...

Page 56: ...Heat Mode Preheat Mode 0 Disabled 1 Low Heat 2 Medium Heat 3 High Heat Yes 3 403 No Motor Trip Selection No Motor Fault 0 Disable 1 Enable No 4 404 Stall Prevention Stall Prevention 0 Disable 1 Enabl...

Page 57: ...reheat Mode 0 Disabled 0 Disabled 0 Disabled 0 Disabled 0 Disabled 3 No Motor Fault 1 Enable 1 Enable 1 Enable 1 Enable 1 Enable 4 Stall Prevention 1 Enable 1 Enable 1 Enable 1 Enable 1 Enable 5 Stall...

Page 58: ...9200 2 38400 3 57600 4 76800 5 115200 Yes 7 507 Parity Stop Bits Modbus RTU 0 None 2 Stop 1 Even 1 Stop 2 Odd 1 Stop 3 None 1 Stop Yes 9 509 Modbus Device Address Modbus RTU Address 1 247 Yes 10 N A B...

Page 59: ...d Speed 2 Hold Speed 2 Hold Speed 1 Stop 5 Com Loss Delay 1 0 sec 1 0 sec 1 0 sec 1 0 sec 1 0 sec 6 RS 485 Baud 1 19200 bps 1 19200 bps 1 19200 bps 1 19200 bps 1 19200 bps 7 Modbus RTU 1 Even 1 Stop 1...

Page 60: ...e W Current Line W Current 0 0 to 6xVFD FLA A N A 9 609 DC Bus Voltage DC Bus Voltage 0 to 1000 V N A 10 610 Output Voltage Output Voltage 0 to 600 V N A 11 611 Output Status Output Status 0 VFD Off 1...

Page 61: ...23 Bypass Phase Loss 24 Bypass Board Error 25 Bypass Stall 26 Bypass Max Time 27 Bypass Ground Fault 28 Bypass Communications Error 29 Bypass Contactor 30 Bypass Current At Power On 31 Bypass No Motor...

Page 62: ...V1 V2 Input 0 Deenergized 1 Energized N A 26 626 V3 V4 Status V3 V4 Input 0 Deenergized 1 Energized N A 27 627 O1 O2 Status O1 O2 Output 0 Open 1 Closed N A 28 628 HOA Status HOA Mode 0 Off 1 Hand 2 A...

Page 63: ...nput 0 Open 1 Closed N A 51 651 O3 O4 Status O3 O4 Output 0 Open 1 Closed N A 52 652 O4 O5 Status O4 O5 Output 0 Open 1 Closed N A 53 653 3A mA Input 3A Input N A Read only N A 54 654 Bluetooth Error...

Page 64: ...Uncalibrated 13 Ground Fault L 21 Bypass Motor Overload L 26 Bypass Max Time L 27 Bypass Ground Fault L 28 Bypass Communications Error 29 Bypass Contactor L 30 Bypass Current at Power On L 31 Bypass...

Page 65: ...utdown 5 VFD fireman s override 6 VFD auto reset 8 Power on delay 12 Signal loss 14 PID run 15 Open damper 18 Bypass stop 19 Bypass manual 20 Bypass override 22 Bypass auto on fault 23 Bypass disabled...

Page 66: ...QLNK 005 DV 2 QLNK 009 DV 3 QLNK 012 DV 4 QLNK 017 DV 5 QLNK 024 DV 6 QLNK 028 DV 7 QLNK 038 DV 8 QLNK 045 DV 9 QLNK 059 DV 10 QLNK 065 DV 11 QLNK 096 DV 12 QLNK 124 DV 13 QLNK 156 DV 14 QLNK 003 D6...

Page 67: ...112 Power CPU Bootloader SW Version Power Bootloader See Product SW Version No 1113 Power CPU Bootloader SW Version 14 1114 Control CPU SW Version See Product SW Version No 1115 Control CPU SW Version...

Page 68: ...h time This is the total number of seconds elapsed since 12 00 AM January 1st 1970 Yes 1131 Date Time Time 32 1132 Set Date Time Yes 1133 Set Date Time 35 1135 Serial Number Serial Number 0 99 999 999...

Page 69: ...temperature transducer The process unit is set to F with 0 150 F temperature transducer range and 80 F PID set point If MMC Multi Motor Control feature is enabled with one of the auxiliary relays the...

Page 70: ...the motor nameplate frequency rating If Maximum Frequency is set to 70Hz Base to 60Hz and Motor Voltage to 230V the VFD during acceleration will output 230V at 60Hz and from this point increase only f...

Page 71: ...FD will be in Stop mode until start command is removed and reapplied PRIMARY 18 Torque Boost Fault Reset 18 Enabled Default Enabled 0 Disabled 1 Enabled Torque Boost feature provides initial voltage v...

Page 72: ...tarts when 0 HOA is in Hand 1 HOA Hand and selected terminal is activated 2 HOA Hand Start Button is pressed 6 HOA Hand start command is given via comms PRIMARY 24 Speed Reference in Hand Hand Speed R...

Page 73: ...ed V Hz pattern ideal for fan pump applications Linear Provides linear change of output Voltage corresponding to output frequency change Linear pattern maintains a linear V Hz ratio Squared Provides s...

Page 74: ...Provides frequency reference via 3A Input set by Communications When Communication is selected as a speed reference source VFD will provide output frequency based on reference set by communications P...

Page 75: ...Unit 49 0 PSI 1 GPM 2 inWC 3 CFM 4 inHg 5 Feet 6 F 7 mBar 8 Pa 9 kPa 10 Meters 11 C 12 Custom 13 Default 0 PSI Unit selection for feedback signal PRIMARY 50 PID Feedback Max PID Feedback Max 53 Min 0...

Page 76: ...fault Below Min Signal loss condition either Half of Analog Signal minimum value or below minimum value PRIMARY 61 Feedback Loss Action Feedback Loss Action 61 Stop 0 Fault 1 Stop 2 Hold Speed Default...

Page 77: ...uencies There are three sets of Skip Frequency pairs of parameters that let you Enable or Disable or set Low and High value for each set The description below applies to each set respectively Disabled...

Page 78: ...ble VFD 16 Skip Freq 3 Enable Skip Freq 3 Enable 16 Disabled 0 Disabled 1 Enabled Default Disabled Skip frequency 3 enable disable Used to bypass mechanical system resonance frequencies VFD 17 Skip Fr...

Page 79: ...ngs Reset User Settings 39 No 0 No 1 Factory Defaults Default 0 No When Factory Defaults is selected VFD will load factory defaults for motor and power line parameters VFD 40 Custom Param 1 Custom Par...

Page 80: ...ved 12 2nd Acc Dec Time 13 3 Wire Start 14 3 Wire Stop 15 HOA Auto 16 HOA Hand 17 Shutdown 18 Fault Reset 19 Bypass 20 Reserved Default None Dry Input 2 function selection VFD does not allow more than...

Page 81: ...tput Contact I O 14 1A Input Min mA 1A Input Min mA 14 4mA Min 0 00mA Max 20 00mA Default 4 00mA 1A mA Input minimum value I O 15 1A Input Min Hz 1A Min Hz 15 0Hz Min 0 00 Hz Max PRIMARY 7 Default 0 0...

Page 82: ...0 1000VDC I O 29 2A Output Scaling 2A Output Scaling 29 100 Min 10 Max 200 Default 100 2A Analog output scaling For max Frequency 60Hz at 50 setting 2A output will provide 5VDC or 12mA depending on 2A...

Page 83: ...00 2A Voltage Input frequency corresponding to V Min I O 66 3A mA Max Value 3A mA Max Value 66 20 00mA Min 0 00 Max 20 00 mA Default 20 00 mA 2A Voltage Input frequency corresponding to V Max I O 67 3...

Page 84: ...0 Disable 1 Enable Default Enabled This works as a current limiting function protecting motor from excessive current above the stall level setting by decreasing the motor speed until the current is re...

Page 85: ...lt 0 1s Delay before Motor Overcurrent Fault occurs Sets the delay time for the Motor Overload trip Timer starts when the current exceeds PROT 12 level Timer will be reset if counting during Motor Ove...

Page 86: ...ne 2 Stop 1 Even 1 Stop 2 Odd 1 Stop 3 None 1 Stop Default None Parity Stop bits selection COMMS 1 0 2 COMMS 9 ModBus RTU Address ModBus RTU Addr 9 247 Min 1 Max 247 Default 247 Modbus Device Address...

Page 87: ...95 Default 60 PSI COMMS 30 Comms Reset Fault N A 30 None 0 None 1 Reset Default None COMMS 36 Bluetooth Enable Bluetooth Enable 36 Enable 0 Disable 1 Enable Default Enable Enable or disable the Bluet...

Page 88: ...FLA A Displays the Line W Current VIEW 9 DC Bus Voltage DC Bus Voltage 9 Min 0 0 Max 1000 0 Displays the DC bus voltage VIEW 10 Output Voltage Output Voltage 10 Min 0 0 Max 600 0 Displays the VFD cal...

Page 89: ...P 51 BMS Communications Loss A 52 Analog Signal Loss 53 Transducer Signal Loss A 54 EEPROM Error 55 Calibration CRC Failed 56 Bluetooth Key CRC Failed 57 Invalid Firmware Displays the fault type C Cr...

Page 90: ...n 0 00 Max 10 00 t VIEW 37 Power Average Power 37 Varies depending on VFD size kW VIEW 39 Target Frequency Target Frequency 39 Min PRIMARY 10 Max PRIMARY 9 VIEW 40 Run Command Source Run Command 40 0...

Page 91: ...alibrated 13 Ground Fault L 21 Bypass Motor Overload L 26 Bypass Max Time L 27 Bypass Ground Fault L 28 Bypass Communications Error 29 Bypass Contactor L 30 Bypass Current at Power On L 31 Bypass No M...

Page 92: ...uency 10 Min 0 0 Max 240 00 Hz Displays the output frequency at the time of the fault Displayed upon VFD fault FAULT 12 System Status System Status 12 0 VFD stop 1 VFD run 2 VFD disabled 3 VFD fault 4...

Page 93: ...Temperature IGBT Temperature 15 Min 0 C Max 160 C Displays the current Inverter temperature in degrees C at the time of the fault Displayed upon VFD fault FAULT 16 PCB Temperature Ambient Temperature...

Page 94: ...rom 0 99 and y is a letter representing the release variant ADMIN 10 Power CPU SW Version Power Board 10 See Product SW Version ADMIN 12 Power CPU Bootloader SW Version Power Bootloader 12 See Product...

Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...

Page 96: ...than the user defined percentage of the FLA setting adjustable in PROTECTION 12 This fault will trip after a short delay adjustable in PROTECTION 13 Check that your ACC time is high enough to allow f...

Page 97: ...used the damage and could possibly damage a newly installed VFD if not corrected Check that there are no shorts in the wires running between your VFD and the motor Over Voltage L A VFD over voltage fa...

Page 98: ...oaded utility transformer causing the issue If the line voltage is fine consider replacing the VFD Input Phase Open L Occurs when The amplitude of DC bus ripples exceeds a set value Ensure all wires o...

Page 99: ...ycled to clear it If Power cycle does not clear the fault please consult factory Bypass Stall The Stall fault occurs when the current exceeds 300 of set FLA for 0 5 sec and the current slope is not de...

Page 100: ...and wait for a few minutes for overload to cooldown and check again 24VDC power during run mode Bypass Current at Power On Bypass measures the current at power on with the contactors open if there is...

Page 101: ...esolve reason for external trip signal Disconnect trip signal connection to digital input Power Board Error M Indicates a problem with the power board Consult factory Control Board Error M Indicates a...

Page 102: ...nimum value OR at maximum value for Feedback Loss Delay time Verify wiring and signal from transducer Check signal input value VIEW 31 VIEW 35 4 20 mA or VIEW 32 VIEW 34 0 10V Check Min Value I O 14 I...

Page 103: ...103 9 2 Fan Replacement...

Page 104: ...104 9 3 Battery Replacement...

Page 105: ...system Assignable addresses for server devices range from an address of 1 to a theoretical maximum of 247 As a server device the VFD communicates all data using only 16 bit holding registers Addressin...

Page 106: ...the drive is configured to accept commands via remote communications it can be commanded to start stop run at a specified output frequency target a setpoint in PID control and reset faults 11 2 Parame...

Page 107: ...to 10 0 8 R W Keypad Frequency Keypad Frequency 0 01 Hz VFD Low Hz to VFD High Hz Limit 9 R W Power On Run Delay Power On Run Delay 1 Sec 0 to 9999 10 R W Acceleration Time Acceleration Time 0 1 sec 1...

Page 108: ...Setpoint A 0 1 0 01 Unit 0 00 to F B Max Value 0 95 30 R W Preset Setpoint B Setpoint B 0 1 0 01 Unit 0 00 to F B Max Value 0 95 31 R W Preset Setpoint AB Setpoint AB 0 1 0 01 Unit 0 00 to F B Max Va...

Page 109: ...utput Voltage 0 1 V 0 to 600 49 R W Timeout Com Loss Delay 0 1 sec 0 1 to 120 0 50 R W Comms Command Frequency Min Freq Limit to High Freq Limit 51 R W PID Setpoint 0 0 to 95 of PID Feedback Max 70 R...

Page 110: ...Status D2 SG Input x 0 Open 1 Closed 2 R V1 V2 Status V1 V2 Input x 0 Deenergized 1 Energized 3 R V3 V4 Status V3 V4 Input x 0 Deenergized 1 Energized 4 R D3 SG Status D3 SG Input x 0 Open 1 Closed 5...

Page 111: ...variant 1 R Power CPU SW Version Power Board x See Product SW Version 2 R Power CPU Bootloader SW Version Power Bootloader x See Product SW Version 3 R Control CPU SW Version x See Product SW Version...

Page 112: ...elerate 1 DC Start 2 Flying Start 5 R W DC Start Level DC Start Level x 0 Low 1 Medium 2 High 6 R W HOA Type HOA Type x 0 Keypad HOA 1 Auto Only 2 Keypad Off Auto 3 External HOA 7 R HOA Status HOA Mod...

Page 113: ...e 17 R W PID Setpoint Source Setpoint Source x 0 Keypad 1 1A Analog Input 2 2A Analog Input 3 Comms 18 R W PID Feedback Source Feedback Source x 0 1A Input 1 2A Input 19 R W PID Feedback Unit Feedback...

Page 114: ...Enabled 28 R W VFD Motor Overload MOL Class VFD MOL x 0 Class 5 1 Class 6 2 Class 10 3 Class 20 29 R W Bypass Motor Overload MOL Class Bypass MOL x 0 Class 5 1 Class 6 2 Class 10 3 Class 20 30 R W Dry...

Page 115: ...re Start 14 3 Wire Stop 15 HOA Auto 16 HOA Hand 17 Shutdown 18 Fault Reset 19 Bypass 33 R W Dry Input 2 Contact D2 SG Input 0 Normally Open 1 Normally Closed 34 R W Wet Input 1 Function V1 V2 Function...

Page 116: ...tion x 0 Fault 1 Run 2 Proof of Run 39 R W Relay Contact O1 O2 Output x 0 Normally Open 1 Normally Closed 40 R W 1A Input Filtering Level 1A Input Filter x 0 Low 1 Medium 2 High 41 R W 2A V Input Filt...

Page 117: ...arch 5 Flying start 6 DC Output 7 Preheat 8 DC trip prevention 9 Stall prevention 10 Bypass off 11 Bypass run 52 R System Status System Status x 0 VFD stop 1 VFD run 2 VFD disabled 3 VFD fault 4 VFD s...

Page 118: ...Phase Unbalance 23 Bypass Phase Loss 24 Bypass Board Error 25 Bypass Stall 26 Bypass Max Time 27 Bypass Ground Fault 28 Bypass Communications Error 29 Bypass Contactor 30 Bypass Current At Power On 31...

Page 119: ...0 0 10 V Input 1 4 20mA Input 78 R 2A Type x 0 0 10 V Input 1 0 10 V Output 2 4 20mA Output 80 R W DC Trip Prevention DC Trip Prevent x 0 Disabled 1 Enabled 81 R W Torque Boost Torque Boost x 0 Disabl...

Page 120: ...ult Reset 19 Bypass 20 Switch 1A to 3A 88 R W Dry Input 3 Contact D3 SG Input x 0 Normally Open 1 Normally Closed 89 R W Dry Input 4 Function D4 SG Function x 0 None 1 Enable 2 Fireman s Override H 3...

Page 121: ...Rsp 3 No Cfg Response 4 No Cfg Val Rsp 5 No Write Rsp 6 No Adv On Rsp 7 No LNAME Rsp 8 No SNAME Rsp 9 No Disconnect Rsp 10 No Satus Ok Rsp 11 No Version Rsp 12 No Transparent Rsp 13 No Tx Comp Rsp 14...

Page 122: ...9 R W Critical Faults Retry Delay Crit Fault Retry Delay Min 1 to 360 11 R W Light Faults Number of Auto Retries Light Fault Retries x 0 to 10 12 R W Light Faults Retry Delay Light Fault Retry Delay...

Page 123: ...in the following cases even if the guarantee term has not expired Damage was caused due to misuse negligence or accident Damage was caused due to abnormal voltage and or peripheral device malfunction...

Page 124: ...E RATING TABLE DE RATING The following de ratings are established based on the ambient and adjustable carrier frequency Where applicable linear interpolation of the rated output current is allowed for...

Page 125: ...125 franklin controls com 1 800 962 3787 Thank you for choosing Franklin Control Systems formerly Cerus Industrial...

Reviews: