Fault
Cause
Remedy
Limit
Switch
Occurs
when:
The
Damper
Switch
input
is
not
detected
within
an
adjustable
time
delay
(VFD
‐
07)
when
using
Damper
Mode
(VFD
‐
06).
Ensure
a
Damper
switch
is
being
used
and
wired
to
appropriate
Digital
Input
set
for
Damper
Switch.
Ensure
the
Damper
Time
Delay
(VFD
‐
07)
is
set
to
a
longer
time
than
it
normally
takes
to
open
the
Damper
and
close
the
Damper
Switch.
Damper
Overload
(L)
Occurs
when:
The
Damper
current
exceeds
0.5A
Ensure
rating
of
the
Damper
Motor
does
not
exceed
0.5A
Ensure
Damper
is
not
blocked
or
stuck
and
is
free
‐
moving.
No
Flow
(L)
When
flow
switch
is
open
for
time
delay
during
no
flow
condition
in
VFD
run
mode,
VFD
will
trip.
Check
if
time
delay
is
not
long
enough
to
provide
flow
during
start
Check
if
there
is
a
suction
pressure
or
water
in
well.
Check
if
pump
did
not
fail
‐
External
Trip
(M)
Occurs
when:
any
digital
input
set
for
EXT
TRIP
is
activated.
Resolve
reason
for
external
trip
signal.
Disconnect
trip
signal
connection
to
digital
input.
Power
Board
Error
(M)
Indicates
a
problem
with
the
power
board.
Consult
factory
Control
Board
Error
(M)
Indicates
a
problem
with
the
firmware.
When
it
happens,
the
control
board
reboots
and
this
faults
immediately.
Consult
factory
VFD
Cooling
Fan
(L)
Fan
is
either
unplugged,
damaged,
or
has
slowed
down
significantly
Check
it’s
plugged
in,
clean
it,
or
replace
it.
Fan
is
rated
at
3800
RPM
and
the
fault
triggers
below
2280.
Power
Board
Communications
Error
(M):
Consult
factory
Overpressure
(A)
Occurs
when:
System
pressure
exceeds
over
pressure
trip
level
setting.
Check
over
pressure
level
in:
Primary
‐
64
Can
be
caused
by
pressure
overshooting
because
P
‐
Gain
setting
is
too
high.
Decrease
P
‐
Gain
value
if
necessary.
Check
if
pump
is
oversized
for
the
application
and
demand
changes
rapidly.
BMS
Communications
Loss
(A)
Occurs
when:
Run
Command
Source
or
Speed
Source
is
set
to
Comms,
and
the
signal
is
not
detected
Check
wiring
and
signal
from
BMS
system
to
VFD
Verify
that
BMS
is
sending
proper
run
command
and/or
speed
signal
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...