42
CHAPTER 7 – PARAMETER LISTS
CHAPTER 7 - PARAMETER LISTS
7.1
Primary Parameter Group
Code
Modbus
Address
Full
Parameter
Name
OLED
Display
Name
Parameter
Setting
Range
Adj.
During
Run
1
101
Application
Application
0
‐
Basic
1
‐
Supply
Fan
2
‐
Exhaust
Fan
3
‐
Cooling
Tower
4
‐
Surface/Booster
Pump
No
2
102
Rated
Motor
Voltage
Motor
Voltage
200/400V
model:
200
to
480V;
default
230V
400V
model:
380
to
480V;
default
460V
No
3
103
Rated
Motor
HP
Motor
Horsepower
1
to
20HP
No
4
104
Rated
Motor
Current
Motor
Current
0.5A
to
VFD
Rating
No
5
105
Rated
Motor
RPM
Motor
RPM
500
to
3600
RPM
No
6
106
Power
Line
Frequency
Line
Frequency
0
‐
50
[Hz]
1
‐
60
[Hz]
No
7
107
Maximum
Frequency
Max
Frequency
30.00
to
240.00
[Hz]
No
8
108
Base
Frequency
Base
Frequency
30.00
to
VFD
Max
Hz
[Primary
‐
07]
No
9
109
High
Frequency
Limit
High
Frequency
Limit
VFD
Low
Hz
Limit
[Primary
‐
10]
to
VFD
Max
Hz
[Primary
‐
07]
No
10
110
Low
Frequency
Limit
Low
Frequency
Limit
0.50
to
VFD
High
Hz
Limit
[Primary
10]
Yes
11
111
Carrier
Frequency
Carrier
Frequency
2.0
to
10.0
[kHz]
No
15
115
Power
‐
On
Run
Power
‐
On
Run
0
‐
Disable
1
‐
Enable
Yes
16
116
Power
‐
On
Run
Delay
Power
‐
On
Run
Delay
0
to
9999
[Sec]
Yes
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...