PRIMARY-42: Speed Reference in Auto
Auto Speed Ref
42) Keypad
0 - Keypad
1 - 1A Analog Input
2 - 2A Analog Input
3 - Comms
4 - PID
5 - 3A Analog Inputs
Default: (0) Keypad
Selection
for
speed
reference
source
in
Auto
mode.
1A
input
0
‐
10VDC
or
4
‐
20mA
type
will
be
set
by
1A
DIP
switch.
2A
input
is
always
0
‐
10V.
2A
selection
is
available
when
2A
DIP
Sw
is
set
to
Input.
When
set
to
PID,
all
PID
parameters
will
be
available.
Keypad
When
VFD
HOA
Auto
key
is
pressed
or
external
HOA
SW
is
put
in
Auto
position,
VFD
will
provide
output
frequency
corresponding
to
a
reference
given
via
VFD
keypad.
1A
Input
Provides
frequency
reference
via
1A
Input
set
by
DIP
Sw
to
4
‐
20mA
or
0
‐
10VDC
(scalable
in
I/O
group).
If
DIP
Sw
is
in
24V
position,
processor
still
treats
it
as
0
‐
10VDC
because
it
will
be
scaled
to
that
level
by
hardware
components.
2A
Input
Provides
frequency
reference
via
2A
Input
set
by
DIP
Sw
to
0
‐
10VDC
input
(scalable
in
I/O
group).
3A
Input
Provides
frequency
reference
via
3A
Input
set
by.
Communications
When
Communication
is
selected
as
a
speed
reference
source,
VFD
will
provide
output
frequency
based
on
reference
set
by
communications.
PID
VFD
speed
reference
will
be
provided
by
PID
control
based
on
difference
between
PID
Set
‐
point
and
Feedback
values.
When
set
to
PID,
all
PID
parameters
will
be
available.
When
PID
mode
is
enabled,
DC
trip
prevention,
stall
prevention
and
skip
frequencies
are
disabled.
PRIMARY-43: Reference Loss Condition
Anlg Ref Loss
43) Half of Min
0 - Disabled
1 – Below ½ of Min
2 – Below Min
Default: (1) Half of Min
Select
either
below
minimum
value,
or
below
half
of
minimum
value
of
the
analog
signal
selected
as
a
speed
reference
loss
condition.
PRIMARY-44: Reference Loss Action
Anlg Ref Loss Act
44) Stop
0 - Fault
1 - Stop
2 - Hold Speed
Default: (1) Stop
Select
a
VFD
action
at
signal
loss:
0
‐
Fault=
VFD
trips
and
manual
reset
or
rebooting
is
required;
1
‐
Stop
=
VFD
stops
using
the
stop
mode
defined
in
BASIC
30;
Provides
auto
restart
when
signal
value
is
equal
or
greater
than
Reference
Min
value,
and
run
command
is
present.
2
‐
Hold
=
VFD
runs
at
previous
speed.
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...