116
BACnet
Object
Instance
Read/
Write
Full
Parameter
Name
OLED
Display
Name
Units
Parameter
Setting
Range
36
R/W
Wet
Input
2
Function
V3
‐
V4
Function
x
0
‐
None
1
‐
Enable
2
‐
Fireman's
Override
3
‐
Speed
‐
A
4
‐
Speed
‐
B
5
‐
Setpoint
‐
A
6
‐
Setpoint
‐
B
7
‐
Damper
LSW
9
‐
External
Trip
10
‐
Run
Forward
13
‐
3
‐
Wire
Start
14
‐
3
‐
Wire
Stop
15
‐
HOA
Auto
16
‐
HOA
Hand
17
‐
Shutdown
18
‐
Fault
Reset
19
‐
Bypass
37
R/W
Wet
Input
2
Type
V3
‐
V4
Input
0
‐
Active
High
1
‐
Active
Low
38
R/W
Relay
Output
Select
O1
‐
O2
Function
x
0
‐
Fault
1
‐
Run
2
‐
Proof
of
Run
39
R/W
Relay
Contact
O1
‐
O2
Output
x
0
‐
Normally
Open
1
‐
Normally
Closed
40
R/W
1A
Input
Filtering
Level
1A
Input
Filter
x
0
‐
Low
1
‐
Medium
2
‐
High
41
R/W
2A
V
Input
Filtering
Level
2A
Input
Filter
x
0
‐
Low
1
‐
Medium
2
‐
High
42
R/W
2A
Output
Selection
2A
Function
x
0
‐
Output
Frequency
1
‐
Output
Current
2
‐
DC
Bus
Voltage
43
R/W
Pre
‐
Heat
Mode
Preheat
Mode
x
0
‐
Disabled
1
‐
Low
Heat
2
‐
Medium
Heat
3
‐
High
Heat
44
R/W
No
Motor
Trip
Selection
No
Motor
Fault
x
0
‐
Disable
1
‐
Enable
45
R/W
Stall
Prevention
Stall
Prevention
x
0
‐
Disable
1
‐
Enable
46
R/W
Protocol
Protocol
x
0
‐
Modbus
RTU
2
‐
BACnet
MS/TP
47
R/W
Write
Access
Write
Access
x
0
‐
Disabled
1
‐
Enabled
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...