117
BACnet
Object
Instance
Read/
Write
Full
Parameter
Name
OLED
Display
Name
Units
Parameter
Setting
Range
48
R/W
Comms
Loss
Action
Com
Loss
Action
x
0
–
Fault
1
–
Stop
(uses
selected
stop
mode)
2
–
Hold
Speed
49
R/W
Parity/Stop
Bits
Modbus
RTU
x
0
‐
None,
2
Stop
1
‐
Even,
1
Stop
2
‐
Odd,
1
Stop
3
‐
None,
1
Stop
50
R/W
Bluetooth
Enable
Bluetooth
x
0
‐
Disable
1
‐
Enable
51
R
Output
Status
Output
Status
0
‐
VFD
Off
1
‐
Accelerate
2
‐
Decelerate
3
‐
Steady
4
‐
Speed
search
5
‐
Flying
start
6
‐
DC
Output
7
‐
Preheat
8
‐
DC
trip
prevention
9
‐
Stall
prevention
10
‐
Bypass
off
11
‐
Bypass
run
52
R
System
Status
System
Status
x
0
‐
VFD
stop
1
‐
VFD
run
2
‐
VFD
disabled
3
‐
VFD
fault
4
‐
VFD
shutdown
5
‐
VFD
fireman's
override
6
‐
VFD
auto
reset
8
‐
Power
‐
on
delay
12
‐
Signal
loss
14
‐
PID
run
15
‐
Open
damper
18
‐
Bypass
stop
19
‐
Bypass
manual
20
‐
Bypass
override
22
‐
Bypass
auto
on
fault
23
‐
Bypass
disabled
24
‐
Bypass
fault
25
‐
Bypass
shutdown
27
‐
Bypass
auto
on
comms
loss
56
R/W
Run/Stop
0
‐
Stop
1
‐
Run
57
R/W
Reset
Fault
0
‐
None
1
‐
Reset
58
W
Reset
User
Settings
x
0
‐
No
1
‐
Factory
Defaults
60
R/W
Reset
Motor
Run
Time
Motor
Run
Time
x
0
‐
No
1
‐
Yes
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...