7.5 Communications
Parameter
Group
Code
Modbus
Address
Full
Parameter
Name
OLED
Display
Name
Parameter
Setting
Range
Adj.
During
Run
1
501
Protocol
Protocol
0
‐
Modbus
RTU
1
‐
Modbus
TCP/IP
2
‐
BACnet
MS/TP
3
‐
BACnet
IP
Yes
3
503
Write
Access
Write
Access
0
‐
Disabled
1
‐
Enabled
Yes
4
504
Loss
of
Comms
Com
Loss
Action
0
–
Fault
1
–
Stop
(uses
selected
stop
mode)
2
–
Hold
Speed
Yes
5
505
Timeout
Com
Loss
Delay
0.1
to
120.0
[Sec]
Yes
6
506
Baudrate
RS
‐
485
Baud
0
‐
9600
1
‐
19200
2
‐
38400
3
‐
57600
4
‐
76800
5
‐
115200
Yes
7
507
Parity/Stop
Bits
Modbus
RTU
0
‐
None,
2
Stop
1
‐
Even,
1
Stop
2
‐
Odd,
1
Stop
3
–
None,
1
Stop
Yes
9
509
Modbus
Device
Address
Modbus
RTU
Address
1
‐
247
Yes
10
N/A
BACnet
MAC/ID
BACnet
MS/TP
MAC
Address
0
to
127
Yes
11
N/A
BACnet
Max
Master
BACnet
MS/TP
Max
Master
0
to
127
Yes
12
N/A
BACnet
Device
Instance
BACnet
Device
0
‐
4194303
Yes
27
527
Comms
Run/Stop
N/A
0
‐
Stop
1
‐
Run
Yes
28
528
Comms
Command
Frequency
N/A
Min
Freq
Limit
to
High
Freq
Limit
Yes
29
529
Comms
PID
Setpoint
N/A
0.0
to
95%
of
[PID
Feedback
Max]
Yes
30
530
Comms
Reset
Fault
N/A
0
‐
None
1
‐
Reset
Yes
36
536
Bluetooth
Enable
Bluetooth
0
‐
Disable
1
‐
Enable
Yes
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...