83
I/O-52: Dry Input 4 Contact
D4-SG Input
52) N.O.
0 – Normally Open
1 – Normally Closed
Default: N.O.
I/O-53: Relay 3 Output Select
O3-O4-O5 Function
53) Fault
0 - Fault
1 - Run
2 - Proof of Run
Default: (0) Fault
2A
Voltage
Input
minimum
value.
For
2
‐
10VDC
signal
set
it
to
2V
I/O-64: 3A mA Min Value
3A Input Min mA
64) 0Hz
Min: 0.00
Max: 20.00 [mA]
Default: 0.00
2A
Voltage
Input
maximum
value.
For
0
‐
5VDC
signal
set
it
to
5V
I/O-65: 3A Min Hz
3A Min Hz
65) 0Hz
Min: 0.00
Max: PRIMARY-7
Default: 0.00
2A
Voltage
Input
frequency
corresponding
to
V
Min
I/O-66: 3A mA Max Value
3A mA Max Value
66) 20.00mA
Min: 0.00
Max: 20.00 [mA]
Default: 20.00 [mA]
2A
Voltage
Input
frequency
corresponding
to
V
Max
I/O-67: 3A Max Hz
3A Max Hz
67) 60Hz
Min: 0.00
Max: PRIMARY-7
Default: 60.00 Hz
2A
Analog
Output
(0
‐
10V
or
4
‐
20mA
set
by
DIP
Switch)
parameter
selection.
Analog
output
is
scaled
to
Max
value
of
the
selected
parameter.
Example:
DC
Link
Voltage
is
0
‐
1000VDC.
I/O-68: 3A Input Filtering Level
3A Input Filter
68) Fault
0 - Fault
1 - Run
2 - Proof of Run
Default: (0) Fault
2A
Analog
output
scaling.
For
max
Frequency
60Hz
at
50%
setting,
2A
output
will
provide
5VDC
or
12mA
(depending
on
2A
DIP
Sw
position).
Summary of Contents for Q-link
Page 12: ...12 2 1 2 UL Label...
Page 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Page 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Page 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Page 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Page 27: ...27 4 4 Wiring Schematic Smart Bypass...
Page 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Page 35: ...35 4 12 PID Control Diagram...
Page 37: ...37 5 2 Control Interface...
Page 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Page 103: ...103 9 2 Fan Replacement...
Page 104: ...104 9 3 Battery Replacement...