Page 67
Function confi guration.
First step: Confi gure the command and address.
1. Press the
On/Off
button, the display will show the
Duox Relay
and
version.
2. Via the arrows we select the
1. COMMAND
menu and press
Ok.
3. Via the arrows we select the
ACTIVATE RELAY
command and press
Ok.
4. Via the arrows we select the
1.1 RELAY ADDR.
menu and press
Ok.
6. Via the number pad we enter the relay address we are confi guring, which must be between
0 and 999, and once entered press
Ok.
7. Via the arrows we select the
1.1 RELAY BLOCK
menu and press
Ok.
8. a) Via the number pad we enter the
relay block address
we are confi guring, which must
be between 0 and 99.
b) If you press the arrows (up/down) we confi gure the
relay
as
GENERAL ENTRANCE
.
To end press
Ok.
9. Upon turning the programmer off, the function remains activated.
Note: Upon activating the Set or Reset, the Relay Activation or Deactivation command is sent
to the confi gured Relay address and block. The origin address will be the same.
Second step: Confi guration of the activation time.
To confi gure the activation time, follow point:
3.2 CONFIGURING ACTIVATION TIMES
4. TECHNICAL CHARACTERISTICS
- Power supply: 18 - 24 Vdc (non-polarised, via the BUS INPUT or BUS OUTPUT).
- Consumption:
* In standby: 1,24 W.
*Maximum: 4,4 W.
- Operating temperature: [0, 40ºC].
- IP Address: 20.
- (+12V): Auxiliary voltage output 12Vdc (300 mA max).
- Dry contact relay:
- C: Common.
- NC: Normally Closed.
- NO: Normally Open.
*Maximum current 3A.
* Maximum voltage 250 VAC or 30 VDC.