V-2 Terminal block control motor forward and reverse
V-2-1 Electrical Diagram:
380V 50/60Hz
Three phase input power supply
Circuit breaker
%
Motor
M
FWD/STOP
REV/STOP
Terminal control control of positive and reverse motor
Connection: Control terminal DI1 corresponds to forward command, control terminal DI2 corresponds to reverse
command.
V-2-2 Paremeters setting:
No.
Code
Parameter name
Setting
range
F0.11
Command source selection
Keyboard control (LED on)
1
F1.00
DI1 terminal function selection
Forward running(FWD)
1
F1.01
DI2 terminal function selection
Reverse running(REV)
2
V-3 External frequency table and ammeter
V-3-1 Electrical Diagram:
0
~
+10V DC
(Default)
0
~
+10V
Analog frequency meter
380V 50/60Hz
Three phase input power supply
Circuit breaker
Motor
M
%
M
FWD/STOP
REV/STOP
Fault reset
0
~
20mA DC
(Default)
External frequency meter and ammeter
4
~
20mA
Analog ampere meter
Standard default output: DA1 default 0 ~ 10V; DA2 default 4 ~ 20mA.
V-3-2 Connection:
The frequency meter is connected to the DA1 and GND terminals of the inverter, and the ammeter is connected to the
DA2 and GND terminals.