F0.16
Ac/deceleration time reference
frequency
0: F0.19(Maximum frequency)
1: Set frequency
2: 100Hz
0
★
F0.17
Carrier frequency adjustment as
per temperature
0: NO; 1: YES
0
☆
F0.18
Carrier Frequency
0.5kHz ~ 16.0kHz
Depends on
models
☆
F0.19
Maximum output frequency
50.00Hz ~ 320.00Hz
50.00Hz
★
F0.20
Upper limit frequency source
0: F0.21 setting
1: AI1analog quantity setting
2: AI2 analog quantity setting
3: Panel encoder setting
4: High-speed pulse setting
5: Communications reference
6: AI3 analog quantity setting
0
★
F0.21
Upper limit frequency
F0.23 (Lower limit frequency) ~ F0.19(Maximum frequency)
50.00Hz
☆
F0.22
Upper limit frequency offset
0.00Hz ~ F0.19 (Maximum frequency)
0.00Hz
☆
F0.23
Lower limit frequency
0.00Hz ~ F0.21 (Upper limit frequency)
0.00Hz
☆
F0.24
Running direction
0:Same direction; 1: Opposite direction
0
☆
F0.25
Reserve
F0.26
AI Simulation accuracy
0: 0.01Hz; 1: 0.05Hz;
2: 0.1Hz; 3: 0.5Hz
1
☆
F0.27
GF type
1. G type (Constant torque load type)
2. F type (Fans/pumps load type)
-
•
7.1.3 F1 Group - Input terminals group
Code
Parameter name
Setting range
Factory
setting
Change
F1.00
DI1 terminal function selection
0 ~ 51
1
★
F1.01
DI2 terminal function selection
2
★
F1.02
DI3 terminal function selection
8
★
F1.03
DI4 terminal function selection
9
★
F1.04
DI5 terminal function selection
12
★
F1.05
DI6 terminal function selection
13
★
F1.06
DI7 terminal function selection
0
★
F1.07
DI8 terminal function selection
0
★
F1.08
Undefined
F1.09
Undefined
The function of digital multifunction input terminal DI1-DI8 (DI5 can be used as a high-speed pulse input terminal), can be set by parameter
F1.00-F1.07, and the optional function is shown in the following table:
Setting
value
Function
Description
0
No function
The terminal for not use can be set to “no function” to prevent accidental operation.
1
Forward run (FWD)
External terminals are used to control the FWD/REV run mode of inverter.
2
Reverse run (REV)
3
Three-wire operation
control
This terminal is used to determine the inverter’s three-wire control mode. For details, please refer to the
instructions of function code F1.10 (“Terminal command mode).
4
Forward JOG(FJOG)
FJOG means Forward JOG running, RJOG means Reverse JOG running. For Jog running frequency
and Jog Ac/deceleration time, please refer to the description of the function code F7.00, F7.01, F7.02.
5
Reverse JOG(RJOG)
6
Terminal UP
Modify frequency increment/decrement command when the frequency is referenced by external
terminal. Adjust up/down the set frequency when the digital setting is selected as the frequency source.
7
Terminal DOWN
8
Free stop
The inverter output is blocked, at the time, the parking process of motor is not controlled by the
inverter. This way is same as the principle of free stop described in F3.07.
9
Fault reset (RESET)
The function make use of terminal for fault reset. It has same function with RESET key on the keyboard.
This function can be used to realize remote fault reset.