5.1.8 F6 Group - Keyboard and display
Code
Parameter name
Setting range
Factory
setting
Change
F6.00
STOP/RESET key functions
0: STOP/RES key is enabled only under keyboard
operation mode
1:STOP/RES key is enabled under any operation
mode
1
☆
F6.01
Running status display parameters 1
0x0000~0xFFFF
001F
☆
F6.02
Running status display parameters 2
0x0000~0xFFFF
0000
☆
F6.03
Stop status display parameters
0x0000~0xFFFF
0033
☆
F6.04
Load speed display coefficient
0.0001~6.5000
3.0000
☆
F6.05
Decimal places for load speed display
0:0 decimal places
2:2 decimal places
1:1 decimal places
3:3 decimal places
1
☆
F6.06
Inverter module radiator temperature
0.0°C~100.0°C
-
•
F6.07
Total run time
0h~65535h
-
•
F6.08
Total power-on time
0h~65535h
-
•
F6.09
Total power consumption
0~65535 kwh
-
•
F6.10
Product series number
Frequency inverter series number
-
•
F6.11
Software version number
Control board software version
-
•
F6.13
Communication read-write data selection
Bit: CRC error response selection
0: CRC error response selection; 1:CRC error
response selection
Ten: broadcast message screening option
0: No shielding; 1: Shielding.
100 bits: Frequency converter fault information
read selection
0: Read; 1: Not read.
011
☆
F6.16
Monitor selection 2
1Kbit/100bit
10bit/1bit
d0.04
☆
Parameter
number
Parameter series number
F6.17
Power correction coefficient
0.00~10.00
1.00
☆
F6.18
Multifunction key definition 1
0: UP key is defined as add function key
1: UP key is defined free stop
2: UP key is defined Forward running
3: UP key is defined Reverse running
4: UP key is defined Forward Jog running
5: UP key is defined Reverse Jog running
6: UP key is defined UP function key
7: UP key is defined DOWN function key
0
☆
F6.19
Multifunction key definition 2
The same as F6.18
0
☆
F6.20
Keypad lock selection
0: RUN, STOP button valid
1: RUN, STOP, keypad encode valid
2: RUN, STOP, UP, DOWN button valid
3: STOP button valid
0
☆
F6.21
QUICK key function selection
0: No function;
1: Jog running
2: Shift switch display state
3: FWD/RVS switchover
4: Clear-up UP/DOWN setting
5: Free stop
6: Running command given in sequence
1
☆