7.1.11 F9 Group - Communication parameter
Code
Parameter name
Setting range
Factory
setting
Change
F9.00
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
☆
F9.01
Data format
0: No parity (8-N-2); 2: Odd parity (8-O-1)
1: Even parity (8-E-1); 3: No parity (8-N-1)
0
☆
F9.02
This unit address
1-250, 0 for broadcast address
1
☆
F9.03
Response delay
0ms-20ms
2ms
☆
F9.04
Communication timeout time
0.0(Invalid);
0.1~60.0s
0.0
☆
F9.05
Data protocol selection
Units digit: MODBUS
0: Non-standard MODBUS protocol
1: Standard MODBUS protocol
Tens digit: Profibus-DP
0: PP01 format; 1: PP02 format
2: PP03 format; 3: PP05 format
31
☆
F9.06
Current resolution
0: 0.01A 1: 0.1A
0
☆
F9.07
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
☆
7.1.12 FA Group - Torque control parameters
Code
Parameter name
Setting range
Factory
setting
Change
FA.00
Speed/torque control mode selection
0: Speed control
1: Torque control
0
★
FA.01
Torque setting source selection under torque
control mode
0: Keyboard setting (FA.02)
1: Analog AI1 setting
2: Analog AI2 setting
3: Panel potentiometer setting
4: High-speed pulse setting
5: Communications reference
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
8: High-speed pulse setting
0
★
FA.02
Torque figures setunder torque control mode
-200.0%~200.0%
150%
☆
FA.03
Torque control acceleration time
0.00s~650.00s
0.00s
☆
FA.04
Torque control deceleration time
0.00s~650.00s
0.00s
☆
FA.05
Torque control forward maximum frequency
0.00Hz~F0.19(Maximum frequency)
50.00Hz
☆
FA.06
Torque control backward maximum frequency
0.00Hz~F0.19 (Maximum frequency)
50.00Hz
☆
FA.07
Torque filter time
0.00s~10.00s
0.00s
☆
7.1.13 Fb group - Control optimization parameters
Code
Parameter name
Setting range
Factory
setting
Change
Fb.00
Fast current limiting manner
0: Invalid 1: Enable
-
☆
Fb.01
Under-voltage point setting
50.0%~140.0%
100.0%
☆
Fb.02
Over-voltage point setting
200.0V~2500.0V
810V
☆
Fb.03
Deadband compensation mode selection
0: No compensation
1: Compensation mode 1
2: Compensation mode 2
1
☆
Fb.04
Current detection compensation
0~100
5
☆
Fb.05
Vector optimization without PG mode selection
0: No optimization
1: Optimization mode 1
2: Optimization mode 2
1
☆
Fb.06
Upper limiting frequency for DPWM switching
0.00Hz~15.00Hz
12.00Hz
☆
Fb.07
PWM modulation manner
0:Asynchronous; 1:Synchronous
0
☆
Fb.08
Random PWM depth
0: Invalid
1~10: PWM carrier frequency random depth
0
☆
Fb.09
Deadband time adjustment
100%~200%
150%
☆