6 Installation and commissioning
6.1 Installation direction and space
JI500 series inverter according to different power rating, the requirements of around installation reserve space is different,
specifically as shown below:
A
A
B
B
B
Cool wind
Hot wind
Mounted
vertically
upwards
Power rating
Dimension requirement
0.75~11kW
A≥100mm;B≥10mm
15~22kW
A≥200mm;B≥10mm
30~75kW
A≥200mm;B≥50mm
93~400kW
A≥300mm;B≥50mm
Fig. 6.2: JI500 Series Each power level installation space requirement
JI500 Series frequency inverter heat radiator circulated from bottom to top, when more than one inverter work together,
usually mounted side by side. In the case of the need to install them by upper and lower rows, due to the heat of the lower
inverters rising to the upper equipment, fault maybe caused, heat insulation deflector and other objects to be installed.
Deflector
Cool wind
Hot wind
Fig 6.2: Heat insulation deflector up and down installation diagram