7.1.2 F0 Group -Basic function group
Code
Parameter name
Setting range
Factory
setting
Change
F0.00
Motor control manner
0. Vector control W/O PG
1. Vector control W/ PG
2. V/F control
2
★
F0.01
Keyboard set frequency
0.00Hz~ F0.19 (Maximum frequency)
50.00Hz
☆
F0.02
Frequency command resolution
1: 0.1Hz;
2: 0.01Hz
2
★
F0.03
Frequency source master setting
0: Frequency setting by keyboard (F0.01, UP/DOWN
can be modified, no memory when power off )
1: Frequency setting by keyboard (F0.01, UP/DOWN
can be modified, memory when power off )
2: Analogquantity AI1 setting
3: Analogquantity AI2 setting
4: Panel potentiometer setting
5: High speed pulse setting
6: Multi-speed running setting
7: Simple PLC program setting
8: PID control setting
9: Remote communication setting
10: Analog quantity AI3 setting
1
★
F0.04
Frequency source auxiliary setting
The same as F0.03
0
★
F0.05
Reference object selection for
frequency source auxiliary setting
0. Relative to maximum frequency
1. Relative to master frequency source 1
2. Relative to master frequency source 2
0
☆
F0.06
Frequency source auxiliary setting
range
0% ~ 150%
100%
☆
F0.07
Frequency source superimposed
selection
Units digit: Frequency source selection
Tens digit: Arithmetic relationship of master and auxiliary for
frequency source
00
☆
F0.08
Frequency source offset frequency
when superimposing
0.00Hz ~ F0.19(Maximum frequency)
0.00Hz
☆
F0.09
Shutdown memory selection for
digital set frequency
0: W/O memory
1: With memory
1
☆
F0.10
Frequency command UP / DOWN
reference when running
0: Running frequency
1: Set frequency
0
★
F0.11
Command source selection
0. Keyboard control (LED off)
1. Terminal block control (LED on)
2. Communications command control (LED flashes)
3. Keyboard Communications command control
4. Keyboard Communications command
Terminal block control
0
☆
F0.12
Binding frequency source for
command source
Units digit: binding frequency source selection for operation
panel command
0: No binding;
1: Keyboard setting frequency;
2: Analog quantity AI1 setting
3: Analog quantity AI2 setting
4: Panel encoder setting
5: High speed pulse setting
6: Multi-speed setting
7: Simple PLC setting
8: PID setting
9: Communication given
Tens digit: Terminal command binding frequency source
selection (0 ~ 9, same as units digit)
Hundreds digit: Communication command binding frequency
source selection (0 ~ 9, same as units digit)
000
☆
F0.13
Acceleration time 1
0.00s ~ 6500s
Depends
on models
☆
F0.14
Deceleration time 1
0.00s ~ 6500s
Depends
on models
☆
F0.15
Ac/Deceleration time unit
0:1 second; 1:0.1 second;
2:0.01 second
1
★