Frequency level detection FDT2 output Please refer to the function code F7.26, F7.27’s instructions.
26
Frequency 1 reaches output
Please refer to the function code F7.28, F7.29’s instructions.
27
Frequency 2 reaches output
Please refer to the function code F7.30, F7.31’s instructions.
28
Current 1 reaches output
Please refer to the function code F7.36, F7.37’s instructions.
29
Current 2 reaches output
Please refer to the function code F7.38, F7.39’s instructions.
30
Timing reach output
When the timer function selection (F7.42) is valid, the drive time to reach this run
after the set time runs out, output ON signal.
31
AI1 input overrun
When the value of analog input AI1 greater than F7.51 (AI1 input protection limit)
or less than F7.50 (AI1 input protection under), output ON signal.
32
Off load
When the inverter is off-load state, output ON signal.
33
Reverse operation
Inverter in reverse run, output ON signal
34
0 current state
Refer to the description of function code F7.32, F7.33.
35
Module temperature reaches
Inverter module heatsink temperature (F6.06) reach the set module temperature
reaches value (F7.40), output signal ON.
36
Software current limit
Please refer to the function code F7.34, F7.35’s instructions.
37
The lower frequency arrival (Stop and
output)
When the operating frequency reaches the lower limit frequency, output ON
signal. In shutdown state of the signal is also ON.
38
Alarm output
When the inverter failure, and the failure of the process to continue to run mode,
the inverter alarm output.
39
Motor overtemperature pre-warning
When the motor temperature reaches F8.35 (Motor overheat pre-alarm
threshold), the output ON signal. (Motor temperature can be viewed at d0.41)
40
Current running time of arrival
When the inverter starts running time is longer than the time set by F7.45, it
outputs ON signal.
F2.06
High-speed pulse output function selection
0~17
0
☆
F2.07
DA1 output function selection
2
☆
F2.08
DA2 output function selection
13
☆
High-speed pulse output frequency range of 0.01kHz ~ F2.09 (High speed pulse output maximum frequency), F2.09 can be set between
0.01kHz ~ 100.00kHz.
Analog Output DA1 and DA2 output range is 0V ~ 10V, or 0mA ~ 20mA. Pulse output or analog output range, with the corresponding scaling
function relationship in the following table:
Setting
value
Functions
Description
0
Running frequency
0~Max. output frequency
1
Set frequency
0~ Max. output frequency
2
Output current
0~2 times the motor rated current
3
Output torque
0~2 times the motor rated toqure
4
Output power
0~2 times rated power
5
Output voltage
0~1.2 times inverter rated voltage
6
High speed pulse input
0.01kHz~100.00kHz
7
Anolog AI1
0V~10V(/ 0~20mA)
8
Anolog AI2
0V~10V(/ 0~20mA)
9
Anolog AI3
0V~10V
10
Lentgh value
0~Max. setting length
11
The count value
0~Max. count value
12
Coummunication set
0.0%~100.0%
13
Motor speed
0~Max. output frequency correspondent speed
14
Output current
0.0A~100.0A(Inverter power
≦
55kW);
0.0A~1000.0A(Inverter power>55kW)
15
DC bus voltage
0.0V~1000.0V
16
Reserve
Reserve
17
Frequency source main
set
0~Max. output frequency
F2.09
Maximum output frequency of high-speed pulse 0.01kHz~100.00kHz
50.00kHz
☆
F2.10
SPB switching quantity output delay time
0.0s~3600.0s
0.0s
☆
F2.11
Relay 1 output delay time
0.0s~3600.0s
0.0s
☆