NEURN030000_220_A
NEURN030000_220_A
V-8 Rise / Fall Control Speed
V-8-1 Electrical diagram:
S1
S2
S3
S4
S5
Circuit breaker
380V 50/60Hz
Three phase input power supply
Motor
M
%
FWD
STOP
REV
Rise
Rise or fall control speed control
Fall
V-8-2 Connection:
Three-wire control mode 1, forward command Corresponding terminal DI1, stop DI2, reverse DI3, DI4 and DI5,
respectively, with the corresponding COM short rise and fall command..
V-8-3 Parameter setting:
No.
Code
Parameter name
Setting
range
F0.11
Command source selection
Terminal block control (LED on)
1
F0.03
Frequency source master setting
UP/DOWN can be modified, power-down
without memory
1
F1.10
Terminal command mode
Three-wire control mode 1
2
F1.00
DI1 terminal function selection
Forward run (FWD)
1
F1.01
DI2 terminal function selection
Three-wire operation control
3
F1.02
DI3 terminal function selection
Reverse run(REV)
2
F1.03
DI4 terminal function selection
terminal UP
6
F1.04
DI5 terminal function selection
terminal DOWN
7
F1.11
Terminal UP/DOWN change rate
Used to set terminal UP/DOWN adjustment
frequency, the rate of frequency change.
1.00Hz/s
F0.10
UP/DOWN reference
Running frequency
0